252
FX
3UC
Series Programmable Controllers
User’s Manual - Hardware Edition
9 CC-Link/LT Built-in master ability (Only FX3UC-32MT-LT)
9.2 CC-Link/LT specifications
FX
3UC
Series Programmable Controllers
User’s Manual - Hardware Edition
9.2
CC-Link/LT specifications
This section explains the communication function and performance of the built-in CC-Link/LT master function.
9.2.1
Performance specifications
*1.
Additional CC-Link/LT masters consume 190mA/5V DC from the PLC main unit or extension power
supply unit.
Make sure that the 5V DC current consumption including other extension blocks and special function
blocks does not exceed the supply capacity of the main unit or extension power supply unit.
→
For details, refer to "Section 1.6 System overall configuration".
*2.
Remote device stations support only the 16-point mode.
*3.
The maximum number of link points varies depending on the system configuration.
→
For details, refer to "Section 1.7 Rules of System Configuration".
Item
Description
Number of connectable
master station
Built-in type CC-Link/LT "Additional CC-Link/LT master (FX
2N
-64CL-M
*1
)
7 maximum"
Applicable point mode
4-point mode or 16-point mode
*2
(selectable by DIP switch)
C
ont
ro
l sp
eci
fic
at
io
ns
Point mode
4-point mode
16-point mode
Maximum number of link
points
256 points
*3
(including the number of I/O points in each PLC)
Number of link points per
station ( ) shows the
number of link points
when composite remote
module is used.
4points (8points)
16points (32points)
Li
nk
s
can
t
ime
32
stations
Points
128 points
256 points
2.5Mbps
0.7ms
1.0ms
625kbps
2.2ms
3.8ms
156kbps
8.0ms
14.1ms
64
stations
Points
256 points
256 points
2.5Mbps
1.2ms
2.0ms
625kbps
4.3ms
7.4ms
156kbps
15.6ms
27.8ms
Co
mm
un
ic
at
ion sp
eci
fic
at
io
ns
Communication speed
2.5 Mbps, 625 kbps and 156 kbps (selectable by DIP switch)
Protocol
BITR method
(Broadcast p Interval Timed Response)
Network topology
T-branch
Error control method
CRC
Item
Description
Number of connected
stations
Remote I/O station
64 stations maximum
Remote device station (RD station)
16 stations maximum
Remote station numbers
Remote I/O station
Setting range: 1 to 64
Remote device station (RD station)
Setting range: 49 to 64
Built-in master station
connection position
Connected at end of trunk line
RAS function
Communication error detection, automatic return to
disconnection and internal loop back diagnosis
Connection cable
Dedicated flat cable
VCTF cable (0.75 mm
2
×
4 JIS C 3306 conformance, refer to Subsection 9.2.3.)
High flexible cable
(For the accredited cable, refer to Subsection 9.2.3.)
Number of occupied I/O
points
Number of connected remote I/O points