N. Par. Description
Default
U.M.
Min.
Max.
33.44
PL PAC-IF013B-E Slave 1 alarm addressing on digital output (0:A - 1:none - 2:B)
0
-
0
2
33.45
PU PAC-IF013B-E Slave 1 alarm addressing on digital output (0:A - 1:none - 2:B)
0
-
0
2
33.46
EE PAC-IF013B-E Slave 1 alarm addressing on digital output (0:A - 1:none - 2:B)
0
-
0
2
33.47
Detected gas leak alarm addressing on digital output [0: A | 1: None | 2: B]
0
-
0
2
50.01
Cold setpoint
24.0
°C
P 99.27
P 99.28
50.02
Hot setpoint
24.0
°C
P 20.26
P 50.01
50.03
Dehumidification setpoint
55
%UR
P 99.02
99
50.04
Humidification setpoint
45
%UR
10
P 99.03
50.05
Cold setpoint for LAN limits
30.0
°C
P 50.01
50.0
50.06
Hot setpoint for LAN limits
18.0
°C
0.0
P 50.02
50.07
Dehumidification setpoint for LAN limits
75
%UR
P 50.03
90
50.08
Humidification setpoint for LAN limits
35
%UR
10
P 50.04
50.09
Minimum room temperature for dehumidifier disable
23.0
°C
P 14.10
35.0
50.14
Setpoint for the adjustment of the fan using the fan adjustment based on return temperature function
24.0
°C
P 20.24
P 20.25
50.15
Setpoint for the adjustment of the fan using the fan adjustment based on return temperature for LAN limits
function
30.0
°C
P 50.14
40.0
Par.N.
Description
Minimum limit that can be set for the internal fan speed.
Calculated as: P10.10 - P10.11%
Minimum limit that can be set for the dehumidification setpoint.
Calculated as: P50.04 + 5
Maximum limit that can be set for the dehumidification setpoint.
Calculated as: P50.03 - 5
Maximum value that can be set for low pressure setpoint for frost-free function
Minimum value that can be set for cold setpoint depending on whether adjustment is enabled
Maximum value that can be set for cold setpoint depending on whether adjustment is enabled