TM_s-MEXT_ME28relC_00_12_19_EN
Technical manual
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
59
N. Par. Description
Default
U.M.
Min.
Max.
22.92
Type of gas used by the unit (0:R410A - 1:R32)
1
-
0
1
22.01
Low temperature alarm setpoint
10
°C
0
30
22.02
High temperature alarm setpoint
32
°C
20
50
22.03
Low humidity alarm setpoint
30
%UR
0
70
22.04
High humidity alarm setpoint
80
%UR
30
99
22.13
Unit operating hours for maintenance setpoint (Thousands)
0
h
0
99
22.14
Compressor 1 operating hours for maintenance setpoint (Thousands)
0
h
0
99
22.17
Step 1 heater operating hours for maintenance setpoint (Thousands)
0
h
0
99
22.18
Step 2 heater operating hours for maintenance setpoint (Thousands)
0
h
0
99
22.19
Humidifier operating hours for maintenance setpoint (Thousands)
0
h
0
4
22.21
Reset alarm by supervision systems [0: Disabled | 1: Enabled]
0
-
0
1
22.55
BMS1 offline alarm management configuration [0: Disabled | 1: Enabled]
0
-
0
1
22.56
Timeout for BMS1 offline alarm
15
s
1
999
22.79
Airflow alarm delay
45
s
15
180
22.80
Dirty filters alarm delay
8
s
2
180
22.83
Configuration of flooding event reset and type [0: Not validated | 1: Automatic signal | 2: Manual signal | 3:
Automatic alarm | 4: Manual alarm]
4
-
0
4
22.85
Configuration of fire/smoke alarm reset[3: Automatic alarm | 4: Manual alarm]
4
-
3
4
23.01
Nominal speed of internal fan
70
%
P 99.01
100
23.02
Internal fan Economy Mode function configuration [0: Disabled | 1: Enabled]
0
-
0
1
23.03
Internal fan speed with Economy Mode enabled
50
%
0
99
23.07
Internal fan modulation function configuration for units with inverter compressor [0: Disabled | 1: Enabled]
1
-
0
1
23.08
Minimum internal fan speed in modulation (Maximum reduction in project speed)
50
%
0
P 10.11
23.10
Internal fan speed in dehumidification (Maximum reduction in project speed)
60
%
P 99.01
P 10.10
23.11
Air differential check time
60
s
0
999
23.61
Heater post-ventilation configuration for unit OFF [0: Disabled | 1: Enabled]
1
-
0
1
23.62
Heater post-ventilation time
60
s
1
999
23.65
Set Constant Flow adjustment (Divided by 100)
25
m³/h
10
400
23.66
Pressure regulation differential for Constant Flow
25
Pa
5
100
23.67
Constant DeltaP adjustment setpoint
10
Pa
5
300
23.68
Minimum internal fan speed in constant DeltaP (maximum nominal speed reduction)
20
%
0
P 10.11
23.69
Pressure regulation differential for Constant DeltaP
5
Pa
3
50
23.70
Fan analogue outlet variation step
1.0
Vdc
0.0
5.0
24.01
Room temperature probe calibration
0.0
°C
-9.9
9.9
24.02
Room humidity probe calibration
0.0
%UR
-20.0
20.0
24.03
Delivery air temperature probe calibration
0.0
°C
-9.9
9.9
24.04
External air temperature probe calibration
0.0
°C
-9.9
9.9
24.08
Circuit 1 low pressure probe transducer
0.0
bar
-9.9
9.9
24.10
Circuit 2 low pressure probe transducer
0.0
bar
-9.9
9.9
24.20
Serial temperature probe address 129 calibration
0.0
°C
-9.9
9.9
24.21
Serial humidity probe address 129 calibration
0.0
%UR
-20.0
20.0
24.23
Temperature differential for the update of the reading of probe T+H 128
0.5
°C
0.1
2.0