TM_s-MEXT_ME28relC_00_12_19_EN
Technical manual
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
103
17.2
EXPANSION NO. 1 (ADDRESS 8)
s-MEXT-G00
Analogue Inputs
Connector
Type
Description
J9
B1
4-20mA
0-5V
DC
Air differential pressure transducer
As an alternative:
Delivery air temperature from
superv.
B2
Free
J10
B3
NTC
External Air Temperature
B4
Free
Free
2
Digital Inputs
Connector
Type
Description
J4
ID1
/
Internal electronic fan 1 alarm
(2)
ID2
/
Internal electronic fan 2 alarm
(2)
ID3
Free
ID4
Free
Free
2
Analogue Outputs
Connector
Type
Description
J2
Y1
0-10V
DC
Direct Freecooling damper
Free
0
Digital Outputs
Connector
Type
Description
J5
NO1
NC1
/
Direct OPEN FC
J6
NO2
NC2
Free
J7
NO3
NC3
Free
J8
NO4
NC4
Free
Free
3
Notes:
(2) Only with fan ADL function enabled (P23.71)