Technical manual
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
106
19.2
FIELDBUS 2
The following devices are connected to the FieldBus 2 port on the controller:
Module
Modbus address
Method for changing address
Master PAC-IF013B-E
21
Dip switch
Slave 1 PAC-IF013B-E
22
Dip switch
19.2.1
Master PAC-IF013BE interface card communication configuration
The configuration of the communication parameters for the Master PAC-IF013B-E interface card is completed using the Dip Switches of the electronic cards.
Master PAC-IF013B-E card configuration (address 21)
Dip-switches
Description
Position
Value
SW6: 1÷2
Protocol
OFF
Manual step control through the Modbus
protocol
SW1: 1÷3
ON
SW1: 8
OFF
ON
with IMOUC
disabled (single Mr
Slim unit)
with IMOUC
enabled
(multiple Mr Slim
unit)
SW3: 6÷7
Baud Rate
OFF
19200
SW3: 8
ON
SW4: 1
Device address
ON
21
SW4: 2
OFF
SW4: 3
ON
SW4: 4
OFF
SW4: 5
ON
SW4: 6
Parity type
OFF
NONE
SW4: 7
ON
SW4: 8
Stop bits
ON
2 bit
Nessuno
Data length
-
8 bit
Slave 1 PAC-IF013B-E card configuration (address 22)
Dip Switch
Description
Position
Value
SW6: 1÷2
Protocol
OFF
Manual step control through the Modbus
protocol with IMOUC enabled
SW1: 1÷3
ON
SW1: 8
ON
SW3: 6÷7
Baud Rate
OFF
19200
SW3: 8
ON
SW4: 1
Device address
OFF
22
SW4: 2
ON
SW4: 3
ON
SW4: 4
OFF
SW4: 5
ON
SW4: 6
Parity type
OFF
NONE
SW4: 7
ON
SW4: 8
Stop bits
ON
2 bit
Nessuno
Data length
-
8 bit