TM_s-MEXT_ME28relC_00_12_19_EN
Technical manual
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
102
17
INPUT/OUTPUT CONFIGURATION TABLE
17.1
MAIN CONTROLLER
s-MEXT-G00
pCO size
Small
Fieldbus
Connector
Address
Description
Circuits
1-2
Fieldbus 2
21
PAC-IF 013B-E Master
Fieldbus 2
22
PAC-IF 013B-E Slave 1
Fieldbus 1
1
Gavazzi CPT network transducer
Fieldbus 1
8
pCOe 1 expansion board
Fieldbus 1
128
Room T+H probe
Fieldbus 1
129
Remote T+H probe
Fieldbus 1
148
CPY humidifier card
Analogue Inputs
Analogue Outputs
Connector
Type
Description
Connector
Type
Description
J2
U1
4-20mA
Circuit 2 evaporation pressure transducer
(1)
J4
Y1
0-10V
DC
Internal Electronic Fan
U2
NTC
Ambient air temperature
Y2
U3
NTC
Delivery air temperature
Y3
J3
U4
4-20mA
Evaporation pressure transducer
Y4
U5
/
Remote on/off
Free
3
Free
0
Digital Inputs
Digital Outputs
Connector
Type
Description
Connector
Type
Description
J5
ID1
/
Phase Sequence
J12
NO1
/
Internal Fan + Delivery Damper
ID2
/
Air flow differential pressure switch
NO2
ID3
/
Clogged filter differential pressure switch
NO3
ID4
/
Heater thermostat
J13
NO4
/
Heating element 1
ID5
/
Fire / Fumes sensor
NO5
/
Heating element 2
ID6
/
Flooding sensor
NO6
ID7
J14
NO7
/
Alarm A
ID8
/
Gas leak sensor
J15
NO8
/
Alarm B
Free
1
Free
3
Notes:
(1) in case of unit with two circuits