TM_s-MEXT_ME28relC_00_12_19_EN
Technical manual
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
30
Mask of the terminal
Description
N. Par.
--------------- P20.82
Aux TH sensor addr.129
status enable : N
Parameter for configuring the presence of the auxiliary temperature / humidity probe (address 129) (0:disabled-
1:enabled)
20.82
Freecooling
Mask confirming access to the Freecooling operation submenu. Press "Up" or "Down" to scroll the other masks
and "Esc" to return to the submenu.
Unit
WITHOUT Freecooling
Mask displayed if the Free Cooling mode is not present.
--------------- P21.21
Cold Ramp value for
max position FC: 050%
Parameter for configuring the value of the cold ramp at which the Freecooling damper is at maximum opening
point
only visible after enabling Free Cooling
21.21
--------------- P21.09
Freecooling damper
reg. enable: N
--------------- P21.10
Freecooling damper
control type: Analogic
Parameter for configuring Freecooling damper regulation (N:disabled - Y:enabled) and parameter for configuring
the Freecooling damper control type (0:Digital - 1:Modulating)
21.09
21.10
--------------- P21.11
Freecooling damper
reg. set point: 03.0°C
--------------- P21.12
Freecooling damper
reg. band: 01.0°C
Parameter for setting the Setpoint (T_
ROOM
-T_
EXTERNAL
) for Freecooling damper control, and the parameter for
setting the Freecooling damper control band
21.11
21.12
--------------- P21.13
Freecooling damper
MIN opening: 000%
--------------- P21.14
Freecooling damper
MAX opening: 100%
Parameter for setting the Minimum Freecooling damper opening and parameter for setting the Maximum
Freecooling damper opening
21.13
21.14
--------------- P21.32
Freecooling damper
with CMP/V3V: Y
--------------- P21.33
Delay Freecooling
damper On after Off
CMP/V3V: 0180s
Parameter for setting the configuration of the simultaneous operation of Direct Freecooling and compressor, or 3-
way valve
Parameter for setting the delay for opening Freecooling after the compressor is switched off/the closing of the
cold water valve
Only visible if the parameter P21.32 is disabled
21.32
21.33
--------------- P21.15
Freecooling damper for
high humid. status: N
--------------- P21.16
%RH set to deact.
freec. damper: 60.0%RH
Parameter for configuring Freecooling damper management for high humidity and
humidity limit for disabling Freecooling damper
21.15
21.16