TM_s-MEXT_ME28relC_00_12_19_EN
Technical manual
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
58
N. Par. Description
Default
U.M.
Min.
Max.
20.10
Flooding sensor configuration [0: Disabled | 1: Enabled]
0
-
0
1
20.13
Remote ON/OFF contact configuration [0: Disabled | 1: Enabled]
0
-
0
1
20.18
Cold adjustment band
2.0
°C
0.5
9.9
20.19
Hot adjustment band
1.5
°C
0.5
9.9
20.20
Dehumidification adjustment band
5
%UR
3
15
20.21
Humidification adjustment band
5
%UR
3
15
20.22
Humidification adjustment integral time (PID)
900
s
0
999
20.23
Humidification adjustment derivative time (PID)
0
s
0
999
20.24
Cold setpoint minimum limit
24.0
°C
10.0
30.0
20.25
Cold setpoint maximum limit
32.0
°C
25.0
40.0
20.26
Hot setpoint minimum limit
12.0
°C
5.0
30.0
20.28
Delivery limit temperature configuration [0: Disabled | 1: Enabled]
0
-
0
1
20.29
Delivery air temperature minimum limit
9.0
°C
0.0
25.0
20.44
Frost-free function configuration [0: Disabled | 1: Enabled]
1
-
0
1
20.47
Low pressure set point for frost-free function
6.5
bar
6.0
P 99.25
20.48
Low differential pressure for frost-free function
0.5
bar
0.5
9.9
20.49
Frost-free function activation delay
10
min
1
99
20.50
Configuration and activation of the counting of number of interventions per hour count for the frost-free
function [0: Disabled | 1: Enabled]
1
-
0
1
20.51
Number of interventions per hour for the frost-free function
3
-
1
5
20.56
Delivery air adjustment setpoint minimum limit
10.0
°C
5.0
40.0
20.57
Delivery air adjustment setpoint maximum limit
25.0
°C
5.0
40.0
20.71
T&H limits alarm configuration with unit OFF [0: Disabled | 1: Enabled]
1
-
0
1
20.72
T&H limits alarm delay when unit ON
600
s
1
999
20.74
Circuit 1 Safety Reduction Load LP function activation setpoint
7.2
bar
5.0
9.0
20.75
Circuit 1 Safety Reduction Load LP function differential
0.6
bar
0.0
1.0
20.82
Auxiliary humidity probe address 129 configuration [0: Disabled | 1: Enabled]
0
-
0
1
21.21
Value of the cold ramp for maximum opening of freecooling valve
50
%
0
100
21.09
Free Cooling damper adjustment configuration [0: Disabled | 1: Enabled]
0
-
0
1
21.10
Free Cooling damper control type configuration [0: Digital | 1: Modulanting]
0
-
0
1
21.11
Setpoint (T
ROOM
-T
EXTERNAL
) for Free Cooling damper adjustment
3.0
°C
0.0
50.0
21.12
Free Cooling damper adjustment band
1.0
°C
0.0
9.9
21.13
Minimum Free Cooling damper opening
0
%
0
100
21.14
Maximum Free Cooling damper opening
100
%
P 21.13
100
21.32
Configuration of simultaneous operation of Direct Freecooling and compressor
1
-
0
1
21.33
Direct Freecooling activation delay after compressor shutdown
180
s
0
9999
21.15
Free Cooling management configuration for high humidity
0
-
0
1
21.16
Humidity limit for Free Cooling damper disable
60.0
%UR
0.0
99.9
21.17
Humidity band to disable Free Cooling damper
1.0
%UR
0.0
9.9
21.18
Free Cooling damper adjustment configuration with compressor alarm [0: Disabled | 1: Enabled]
0
-
0
1
21.19
Setpoint (T
ROOM
-T
EXTERNAL
) to regulate the Free Cooling damper with compressor alarm
1.0
°C
1.0
50.0
21.20
Free Cooling damper adjustment band with compressor alarm
0.5
°C
0.0
9.9