TM_s-MEXT_ME28relC_00_12_19_EN
Technical manual
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
36
Mask of the terminal
Description
N. Par.
--------------- P26.05
Units in stand-by
in LAN: 2
--------------- P26.06
Stand-by mode limits
in LAN status: Y
Parameter for configuring the number of units in stand-by in LAN (0 1 unit - 1 2 units) and for configuring the
Stand-by mode limits in LAN function (N:disabled - Y:enabled)
26.05
26.06
--------------- P26.11
H&L Local Temp prot.
enable : N
--------------- P26.12
Diff. for On with High
local temp : 02.0°C
Parameter for enabling Hot&Cold spot management
Parameter for configuring the differential according to the average temperature for activation of the Hot Spot
function
Only visible for units with adjustment according to average temperature
26.11
26.12
--------------- P26.13
Diff. for On with Low
local temp : 02.0°C
--------------- P26.14
Time before Off
protection with T.room
in range: 300s
Parameter for configuring the differential according to the average temperature for activation of the Cold Spot
function
Parameter for configuring the time for deactivation of the Hot & Cold Spot function
26.13
26.14
--------------- P26.15
Time before On
protection with T.room
out of range: 060s
Parameter for configuring the time of activation of the Hot & Cold Spot function after exceeding of the limits
26.15
--------------- P26.16
Active Fan on Stand by
Enable: N
--------------- P26.17
Active fan speed: 070%
Parameter for enabling the Active Fan on Standby function
Parameter for setting the fan speed during operation in Active Fan on Standby mode
26.16
26.17
--------------- P26.18
Active Pressure Load
enable: N
--------------- P26.19
Disable APL during
Diff.P probe alarm: N
Enable the Active Pressure Load function (APL).
Enable disabling of the APL function during the air differential pressure probe alarm.
Only visible for units with air flow control according to DeltaP enabled
26.18
26.19
--------------- P26.20
H&L Local Press. prot.
enable : N
--------------- P26.21
Diff. for On with High
local press: 010Pa
Parameters for setting
Hi & Low local pressure protection function enable
On differential for floor pressures above average
26.20
26.21
--------------- P26.22
Diff. for On with Low
local press: 010Pa
--------------- P26.23
Time before Off
protection with local
DeltaP in range: 300s
Parameters for setting
On differential for floor pressures below average
Time before stopping protection in case of local pressure differences within the limits
26.22
26.23
--------------- P26.24
Time before On prot.
with local DeltaP
out of range: 060s
Parameter for setting the time delay before the start of the protection in case of local pressure differences outside
the limits
26.24