TM_s-MEXT_ME28relC_00_12_19_EN
Technical manual
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
43
Mask of the terminal
Description
N. Par.
GSM modem management
Send SMS Test: N
Hang Up: N
Text SMS sending mask.
Alarm out
Access mask to "Alarm out" submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the
submenu.
--------------- P31.01
Alarm out A logic: _\_
--------------- P31.02
Alarm out B logic: _\_
Parameters to configure the alarm A contact status (0:NO - 1:NC)
and the alarm B contact status (0:NO - 1:NC)
31.01
31.02
--------------- P31.03
(003) Fire/smoke alarm
out addressing:A
Fire/smoke alarm addressing on digital output (0:A - 1:none - 2:B)
31.03
--------------- P31.04
(004) Phase seq. alarm
out addressing:A
Phase sequence alarm addressing on digital output (0:A - 1:none - 2:B)
31.04
--------------- P31.10
(101) Air flow alarm
out addressing:A
Air Flow alarm addressing on digital output (0:A - 1:none - 2:B)
31.10
--------------- P31.11
(120) Room temp. probe
alarm out addressing:
A
Ambient air temperature probe alarm addressing on digital output (0:A - 1:none - 2:B)
31.11
--------------- P31.12
(125) Ambient humidity
probe alarm
out addressing:A
Ambient humidity probe alarm addressing on digital output (0:A - 1:none - 2:B)
31.12
--------------- P31.13
(130) Diff. pressure
probe alarm
out addressing:A
Differential pressure probe alarm addressing on digital output (0:A - 1:none - 2:B)
31.13