TM_s-MEXT_ME28relC_00_12_19_EN
Technical manual
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
33
Mask of the terminal
Description
N. Par.
Fan
Access mask to fan submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.
--------------- P23.01
Fan nominal
speed: 070%
Parameter for setting the nominal speed of the internal fan
23.01
--------------- P23.02
Economy mode fan
status: N
--------------- P23.03
Fan speed in
economy mode: 50%
Parameter for configuring the internal fan Economy Mode function (N:disabled - Y:enabled)
Parameter for setting the internal fan speed with the Economy Mode function enabled
23.02
23.03
--------------- P23.07
Air Flow modulation
with inverter mod.
status: Y
Parameter for configuring the Internal fan modulation function for inverter compressor units (N:disabled -
Y:enabled)
Only visible with constant flow rate check and constant DeltaP disabled
23.07
--------------- P23.08
MIN fan speed when
modul. active: 050%
Parameter for setting the minimum speed of the internal fan in modulation for inverter compressor units
(maximum reduction of design speed)
23.08
--------------- P23.10
Fan speed when active
dehumidif.: 060%
Parameter for setting the fixed internal fan speed for units with inverter compressor in dehumidification
23.10
--------------- P23.11
Air pressure diff.
scan time: 060s
Parameter for setting the differential air pressure scan time and
parameter for configuring the EC condensation control function (N:disabled - Y:enabled)
23.11
--------------- P23.61
Post-ventilation
for el.heater status:Y
--------------- P23.62
Post-ventilation time
for el.heater: 060s
Parameters for configuring the post-ventilation function for the heaters and the post-ventilation time.
Visible when the electric heaters are present
23.61
23.62
--------------- P23.65
Const. flow rate set:
02500 m3/h
Parameter used to set the Constant flow rate control setpoint (divided by 100)
23.65