Mask of the terminal
Description
N. Par.
--------------- P20.06
Inv. compressor reg.
intergral time: 900s
Parameter for setting
Integral adjustment time
20.06
--------------- P20.07
Inv. compressor reg.
derivative time: 000 s
Parameter for setting the inverter compressor adjustment derivative time (units with inverter compressor)
20.07
--------------- P20.08
Dirty filters sensor
presence: N
--------------- P20.09
Fire/smoke sensor
presence: N
Parameter for configuring the dirty filters sensor (N:disabled - Y:enabled)
and for configuring the fire smoke sensor (N:disabled - Y:enabled)
20.08
20.09
--------------- P20.10
Flooding sensor
presence: N
Parameter for configuring the flooding sensor (N:disabled - Y:enabled)
20.10
--------------- P20.13
Remote ON/OFF
presence: N
Parameter for configuring the ON/OFF remote contact (N:disabled - Y:enabled).
20.13
--------------- P20.18
Regulation band in
cooling: 2.0°C
--------------- P20.19
Regulation band in
heating: 1.5°C
Parameter for setting the cooling regulation band and the heating regulation band
20.18
20.19
--------------- P20.20
Regulation band for
dehumidif.: 5%RH
--------------- P20.21
Regulation band for
humidification: 5%RH
Parameter for setting the dehumidification regulation band and the humidification regulation band
20.20
20.21
--------------- P20.22
Integral time reg.
humidifier 900s
--------------- P20.23
Derivative time reg.
humidifier 000s
Parameter for setting the Humidification integral time (PID)
Humidification regulation derivative time (PID)
20.22
20.23
--------------- P20.24
Cooling set point
lower limit: 24.0°C
--------------- P20.25
Cooling set point
upper limit: 32.0°C
Parameter for setting the Lower setpoint cooling limit and the Upper cooling setpoint limit
20.24
20.25