TM_s-MEXT_ME28relC_00_12_19_EN
Technical manual
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
40
Mask of the terminal
Description
N. Par.
--------------- P27.16
Enable Humidif.
Periodical Drain: N
--------------- P27.17
Time to wait for
Periodical Drain: 024h
Parameter for enabling the periodical drain function when the humidifier is in operation (N:disabled - Y:enabled)
Parameter for selecting the number of hours of continuous operation after which to perform the periodical drain
function
Visible only if the humidifier is internal.
27.16
27.17
--------------- P27.18
Enable Humidif.
Inactivity Drain: N
--------------- P27.19
Time to wait for
Inactivity Drain: 03d
Parameter for enabling the periodical drain function when the humidifier is inactive (N:disabled - Y:enabled)
Parameter for selecting the number of days of inactivity of the humidifier after which to perform draining
Visible only if the humidifier is internal.
27.18
27.19
--------------- P27.09
Dehumidification:
N
Dehumidifier configuration (N:disabled - Y:enabled)
27.09
--------------- P27.11
Damper config.:
N
--------------- P27.12
Damper opening time:
120sec
Parameters used to configure the air delivery damper (N:disabled - Y:enabled) and the
damper opening time
27.11
27.12
--------------- P27.13
Energy management:
N
Parameter to set the presence of the network transducer (N:absent - Y:present)
27.13
--------------- P27.14
System type:
3 -ph Aron
--------------- P27.15
Transformer ratio:
00020
Parameter for configuring the power supply system that can be 1-2-3 phases with balanced/unbalanced load, with
or without neutral (Default: system 3/4 unbalanced wires)
Parameter for configuring the input current transformer ratio (Default: 20)
27.14
27.15
Config CPT network: N
Serial baud CPT:4800
-3:INVALID DATA
-3:INVALID DATA
baud rate CPT OK
Chek Connections (Esc)
Mask for setting the correct transducer communication speed.
“Config CPT network” is used to set the correct speed in the transducer (from 9
600 to 19200). The transformer
ratio and the desired system type is sent to the transducer (P16.01 and P16.02).
The “NO ERROR” and “Transducer OK” messages indicate correct communication with the transducer for
changing speed.
“Ct ratio OK” and “System OK”
indicate the transformer ratio and the the system type indicated in parameters
P16.01 and P16.02 have been correctly sent to the transducer.
The various transducer configuration phases are indicated at the bottom of the mask. For further details see the
section relative to the network transducer.
--------------- P27.20
Enable setpoint
compensation: N
--------------- P27.21
Type of signal for
compensation: 0-1V
Parameters for setting
Setpoint offset function enable
Setpoint compensation signal type
27.20
27.21