Technical manual
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
29
Mask of the terminal
Description
N. Par.
--------------- P20.26
Heating set point
lower limit: 12.0°C
Parameter for setting the Lower setpoint heating limit and the
Upper setpoint heating limit
20.26
--------------- P20.28
Discharge air limit
function: N
--------------- P20.29
Disch. air limit:
09.0 °C
Parameter for configuring the discharge air temperature limit (N:disabled - Y:enabled)
and parameter for setting the discharge air temperature limit
20.28
20.29
--------------- P20.44
Frost function
status: Y
Parameter to configure the frost-free control function (0:disabled- 1:enabled)
20.44
--------------- P20.47
LP setpoint frost
protect: 06.5bar
--------------- P20.48
LP differential frost
protect: 0.5bar
Parameters to set the low delivery and differential pressure set point for the frost-free function
20.47
20.48
--------------- P20.49
Delay to activate
frost protect: 10min
Parameter to set the frost-free activation delay time
20.49
--------------- P20.50
Enable Frost count
status: Y
--------------- P20.51
Number stop count
per hour: 3
Parameter to configure the number of interventions per hour count for the frost-free function (0:disabled-
1:enabled).
Parameter to set the number of interventions per hour for the passage from the automatic reset alarm to the
manual reset.
Warning
: If the number of counts per hour is disabled, the alarm is
only
in Manual reset mode
20.50
20.51
--------------- P20.56
Supply temp set point
lower limit: 10.0°C
--------------- P20.57
Supply temp set point
upper limit: 25.0°C
Parameter to configure the lower and upper limit for setting the delivery air control setpoint.
Only
visible when delivery air adjustment is active.
20.56
20.57
--------------- P20.71
Enable T&H limit alarm
on Unit OFF: Y
--------------- P20.72
Delay T&H limit alarm
after unit ON: 600s
Parameter for configuring the control of the ambient temperature limits with the unit OFF
Parameter for configuring the delay before activation of the ambient temperature limit alarms after the unit is
activated
20.71
20.72
--------------- P20.74
SRL (LP) setpoint
circuit 1: 7.2bar
--------------- P20.75
SRL (LP) differencial
circuit 1: 0.6bar
Parameters for configuring the values for activation and deactivation of the Safety Reduction Load Low Pressure
function for circuit 1
Visible when the Safety Reduction Load Low Pressure function is enabled
20.74
20.75