3
3.4 Buffer Memory
3.4.14 CH[]Scaling upper/lower limit value (Un\G54 to Un\G65)
3
- 34
1
OV
E
R
VI
EW
2
SYSTE
M
CO
N
F
IG
UR
A
T
IO
N
3
S
P
E
CI
F
ICA
T
IO
N
S
4
SE
T
U
P
AN
D
PR
OCE
D
U
R
ES
B
E
FOR
E
OP
ER
A
T
ION
5
UT
ILI
T
Y
P
ACK
AGE
(G
X CO
NFI
G
U
R
A
T
O
R
-
DA
)
6
PROGRAMMING
7
ON
LI
N
E M
O
D
U
LE
CHANGE
8
T
R
OU
B
LES
H
O
O
T
IN
G
3.4.14 CH
[ ]
Scaling upper/lower limit value (Un\G54 to Un\G65)
(1) When the scaling function is used, set a digital value input range. (Refer to Section
(2) The setting range is -32000 to 32000.
Set them so that the scaling upper limit value is greater than the scaling lower limit
value.
If any value outside the setting range is set, an error occurs and the corresponding
Error code (Un\G19) is stored.
(3) To validate the settings, on/off of Operating condition setting request (Y9) is required.
(Refer to Section 3.3.2.)
3.4.15 CH
[ ]
Increase/decrease digital limit value (Un\G70 to Un\G81)
(1) For rate control, set the range where the digital value can be incremented and decre-
mented in a conversion cycle per channel (6ms). (Refer to Section 3.2.4.)
(2) The setting range is 0 to 64000 (0
H
to FA00
H
).
If any value outside the setting range is set, an error occurs and the corresponding
error code is stored in Error code (Un\G19).
(3) Operating condition setting request (Y9) must be turned on/off to validate the settings.
(Refer to Section 3.3.2.)
When setting CH Increase/decrease digital limit value (Un\G70 to Un\G81) from
the sequence program, values from 0 to 32767 can be set as decimal numbers
without change. Note that this is not applicable to 32768 to 65535. These values
must be converted to hexadecimal numbers before setting.
3.4.16 CH
[ ]
Warning output upper/lower limit value (Un\G86 to
Un\G97)
(1) Set the upper and lower limit values of the digital input value for providing the warning
output. (Refer to Section 3.2.3.)
(2) The setting range is -32000 to 32000.
Make setting so that the upper limit value is greater than the lower limit value.
If any value outside the setting range is set, an error occurs and the corresponding
error code (Un\G19) is stored.
(3) Operating condition setting request (Y9) must be turned on/off to validate the settings.
(Refer to Section 3.3.2.)
Содержание Q66DA-G
Страница 2: ......
Страница 6: ...A 4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Страница 189: ......