5
- 28
5.6 Monitoring/Test
5.6.4 Pass data
5
UTILITY PACKAGE (GX Configurator-DA)
(3) User range restoration
(a) Set the user range to be used in the Setting value field of CH Pass data classifi-
cation setting, and click the
button.
When the user range setting is completed, the set user range is displayed in the
current value field of CH Pass data classification setting.
(b) Set the recorded values in the Setting value fields of CH Industrial shipment set-
tings offset/gain values/user range settings offset/gain values.
(c) Select all the Setting value fields of CH Industrial shipment settings offset/gain
values/user range settings offset/gain values, and click the
button.
When writing is completed, the set values are displayed in the Current value fields
of CH Industrial shipment settings offset/gain values/CH User range settings
offset/gain values.
(d) Change the Setting value field of Pass data write request to "Request", and click
the
button.
Make sure that the indication in the Current value field of Pass data write request
changes from "Request" to "OFF" on completion of writing.