7.3 Online Module Change Procedure
7.3.4 When user range setting is used and initial setting was made with GX Configurator-DA (other system
7
ONLINE MODULE CHANGE
7.3.4
When user range setting is used and initial setting was made
with GX Configurator-DA (other system is unavailable)
(1) Conversion disable
(a) In the Operating condition setting window of GX Configurator-DA, set "Disable" in
the Setting value field of CH D/A conversion enable/disable setting, and click
the
button.
(b) After making sure that the indication in the Current value field of CH D/A
conversion enable/disable setting is "Disable", change the Setting value field of
Operating condition setting request to "Setting request", and click the
button to stop conversion.
Confirm that conversion has stopped with the actual analog output value.