3.4 Buffer Memory
3.4.17 Mode switching setting (Un\G158, Un\G159)
3
3.4.17 Mode switching setting (Un\G158, Un\G159)
(1) Set the values of the mode to switch.
(2) After setting the values, turning Operation condition setting request (Y9) from off to on
enables mode switching.
(3) When mode switching is performed, this area is cleared to zero and Operating condi-
tion setting completed flag (X9) turns off.
After confirming that Operating condition setting completed flag (X9) has turned off,
turn off Operating condition setting request (Y9).
If the values written are other than the above, mode switching is not performed
and only the operating condition is changed.
3.4.18 Pass data classification setting (Un\G200)
(1) Areas used to restore the user range settings offset/gain values when online module
change is made.
Refer to Chapter 7 for details of online module change.
(2) Specify the user range setting to be saved/restored when saving/restoring the offset/
gain values of any of the user range settings 1 to 3.
Refer to Section 4.6 for the offset/gain value setting method.
Mode to be switched to
Set values
Buffer memory address 158 Buffer memory address 159
Normal mode
0964
H
4144
H
Offset/gain setting mode
4144
H
0964
H
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
00: User range setting 1 specification
01: User range setting 2 specification
10: User range setting 3 specification
Un\G200
0
0
0
0
CH6
CH5
CH4
CH3
CH2
CH1
b12 to b15 information is fixed at 0