App
- 9
Appendix 1 Dedicated Instruction List and Available Devices
Appendix 1.3 G(P).OGSTOR
(1) Functions
(a) Restores the offset/gain values of the user range setting stored in the CPU to the
Q66DA-G.
(b) There are two types of interlock signals for the G(P).OGSTOR instruction: the
completion device (D) and the status display device at completion (D) + 1.
1) Completion device
Turns on in the END processing of the scan where the G(P).OGSTOR instruc-
tion is completed, and turns off in the next END processing.
2) Status display device at completion
Turns on and off depending on the completion status of the G(P).OGSTOR
instruction.
Normal completion
: Stays off and does not change.
Abnormal completion : Turns on in the END processing of the scan where
the G(P).OGSTOR instruction is completed, and
turns off in the next END processing.
(c) When the offset/gain values are restored, the reference accuracy falls to about
less than three times of the accuracy before that.
(2) Operation error
In any of the following cases, an error occurs and the corresponding error code is
stored into the completion status area (S)+1.
(3) Program example
The following program is designed to read the offset/gain values of the Q66DA-G
mounted in the position of I/O number X/Y0 to X/YF when M11 is turned on.
Error code
Case resulting in operation error
161
The G(P).OGSTOR instruction was executed in the offset/gain setting mode.
162
The G(P).OGSTOR instruction was executed consecutively.
163
The G(P).OGSTOR instruction was executed for the model that differs from the
model for which the G(P).OGLOAD instruction had been executed.
164
The value set to the pass data classification setting (S)+2 is outside the range.
ON
OFF
OFF
OFF
ON
Sequence program
END processing END processing
END processing END processing
Execution completion of
the G.OGSTOR instruction
G.OGSTOR instruction
Completion device (D)
Status display device
at completion (D)+1
ON Abnormal
completion
Normal completion
1 scan
Control data setting
Offset/gain value restoration
Performs processing at abnormal completion
Dedicated instruction
(GP.OGSTOR)