Appendix 1 Dedicated Instruction List and Available Devices
Appendix 1.1 G(P).OFFGAN
App
- 2
AP
PENDICES
INDEX
Appendix 1.1 G(P).OFFGAN
Switches the mode of the Q66DA-G. (Normal mode to offset/gain setting mode, offset/gain
setting mode to normal mode)
Setting data
(1) Function
Switches the mode of the Q66DA-G.
• Normal mode to offset/gain setting mode (Offset/gain setting mode flag (XA)
turns on.)
• Offset/gain setting mode to normal mode (Offset/gain setting mode flag (XA)
turns off.)
(1) When the offset/gain setting mode is switched to the normal mode, Module
READY (X0) turns from off to on.
Note that initial setting processing will be executed if there is a sequence pro-
gram that makes initial setting when Module READY (X0) turns on.
(2) D/A conversion is discontinued if the mode is switched (from the normal mode
to the offset/gain setting mode or from the offset/gain setting mode to the nor-
mal mode).
To resume D/A conversion, switch to the normal mode and then turn on Oper-
ating condition setting request (Y9).
Setting
data
Usable devices
Internal device
(System, user)
File
register
Link direct device
J \
Intelli-
gent func-
tion
module
device
U \G
Index
register
Z
Constant
Others
Bit
Word
Bit
Word
K, H
$
(S)
—
—
—
—
—
Setting
data
Description
Setting range
Data type
Un
Start I/O number of the module
0 to FE
H
Binary 16 bits
(S)
Mode switching
0: Switching to normal mode
1: Switching to offset/gain setting mode
The setting of any other value results in "switching to offset/gain setting
mode".
0, 1
Binary 16 bits
Command
[Execution
condition]
[Instruction
symbol]
G.OFFGAN
Command
GP.OFFGAN
G.OFFGAN
Un
( S)
GP.OFFGAN
( S)
Un
Содержание Q66DA-G
Страница 2: ......
Страница 6: ...A 4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...