Appendix 1 Dedicated Instruction List and Available Devices
Appendix 1.2 G(P).OGLOAD
App
- 4
AP
PENDICES
INDEX
Appendix 1.2 G(P).OGLOAD
Reads the offset/gain values of the user range setting of the Q66DA-G to the CPU.
Setting data
Control data (1/2)
*1
Setting
data
Usable devices
Internal device
(System, user)
File
register
Link direct device
J \
Intelli-
gent func-
tion
module
device
U \G
Index
register
Z
Constant
Others
Bit
Word
Bit
Word
K, H
$
(S)
—
—
—
—
—
(D)
—
—
—
—
Setting
data
Description
Setting range
Data type
Un
Start I/O number of the module
0 to FE
H
Binary 16 bits
(S)
Start number of the device in which control data is stored.
Within the range of the speci-
fied device
Device name
(D)
Device that is turned on 1 scan on completion of dedicated instruction
processing.
(D) + 1 also turns on at an abnormal completion.
Within the range of the speci-
fied device
Bit
Device
Item
Setting data
Setting
range
Set by
(S)
System area
-
-
-
(S) + 1
Completion status
Stores the status when the instruction is complete.
0 : Normal completion
Other than 0: Abnormal completion
-
System
(S) + 2
Pass data classification setting
Specify the user range setting where offset/gain val-
ues will be read.
00
H
: Use range setting 1 specified
01
H
: Use range setting 2 specified
10
H
: Use range setting 3 specified
0000
H
to
0AAA
H
User
(S) + 3
System area
-
-
-
(S) + 4
CH1 Industrial shipment settings offset value
-
-
System
(S) + 5
CH1 Industrial shipment settings gain value
-
-
System
(S) + 6
CH2 Industrial shipment settings offset value
-
-
System
(S) + 7
CH2 Industrial shipment settings gain value
-
-
System
G.OGLOAD
G.OGLOAD
GP.OGLOAD
Un
(D)
(D)
(S)
(S)
Un
GP.OGLOAD
Command
[Execution
condition]
[Instruction
symbol]
Command
b11 b10
b15
to
b12
b9 b8 b7 b6
0: Fixed CH6
CH5 CH4
b5 b4 b3 b2 b1 b0
CH3
CH2 CH1