6
- 10
6.3 For Use on Remote I/O Network
6
6.3
For Use on Remote I/O Network
(1) System configuration
(2) Conditions for the intelligent function module switch setting
Based on the setting conditions given in the above, make the intelligent function module
switch settings.
Select the [I/O assignment] tab on the [Intelligent function module switch settings] screen,
and click [Switch setting] to set the following values.
Input range setting
HOLD/CLEAR function setting
Normal/High resolution mode
CH1
4 to 20mA
CLEAR
High resolution mode
CH2
0 to 5V
CH3
to
CH6
not used
-
-
Switch No.
Setting value
Switch 1
0030
H
(CH1: 4 to 20mA, CH2: 0 to 5V, CH3 to CH6: Default)
Switch 2
0000
H
Switch 3
0000
H
(CH1,CH2: CLEAR)
Switch 4
0F00
H
(High resolution mode)
Switch 5
0000
H
(0: Fixed)
Remote master station (Network No.1)
Remote I/O station (Station No.1)
QY10 (Y110 to Y11F)
Q66DA-G(X/Y120 to X/Y12F)
QX10 (X100 to X10F)
QJ72LP25
QX10(X20 to X2F)
QJ71LP21
QY10(Y30 to Y3F)