[8-3 Refrigerant Control Problems ]
HWE18240_GB
chapter 8 -
13
8 Troubleshooting Based on Observed Symptoms
Cause
Check method and remedy
2.
Indoor unit LEV malfunction
Insufficient refrigerant flows due to LEV malfunction
(not enough opening).
Refer to the following page(s). [8-8 Troubleshooting
LEV Problems]
3.
Temperature reading error on the indoor unit piping
temperature sensor
If the temperature reading on the sensor is higher
than the actual temperature, it makes the subcool
seem smaller than it is, and the LEV opening de-
creases too much.
Check the thermistor.
4
RPM error of the outdoor unit FAN
Refer to the following page(s).
[8-7 Troubleshooting Outdoor Unit Fan Problems]
Motor failure or board failure, or airflow rate de-
crease, pressure drop due to clogging of the heat
exchanger leading to high discharge temperature
The fan is not properly controlled as the tempera-
ture cannot be precisely detected with the piping
sensor.
5.
Insulation failure of the refrigerant piping
6.
Long piping length
Excessively long piping on the high pressure side
causes pressure loss leading to increase in the high
pressure.
Confirm that the characteristic of capacity drop due
to piping length.
ĺ
Change the pipe
7.
Piping size is not proper (thin)
8.
Clogging by foreign object
Check the temperature difference between the up-
stream and the downstream of the pipe section that
is blocked. Since blockage in the extended section
is difficult to locate, operate the unit in the cooling
cycle, and follow the same procedures that are
used to locate the blockage of pipe during cooling
operation.
ĺ
Remove the blockage in the pipe.
9.
The indoor unit inlet temperature is excessively high.
(exceeding 28°C [82°F])
Check the inlet air temperature and for short cy-
cling. Change the environment where the indoor
unit is used.
10.
Insufficient refrigerant amount
Protection works and compressor frequency does
not rise due to low discharge temperature
Refrigerant recovery operation is likely to start.
Refer to item 1 (Compressor frequency does not
rise sufficiently.) on the previous page.
Refer to the following page(s). [6-3 Evaluating and
Adjusting Refrigerant Charge]
11.
Compressor failure (same as in case of cooling)
Check the discharge temperature.
12.
LEV2 actuation failure
A drop in the low pressure that is caused either by a
blockage of liquid pipe or by a pressure loss and the
resultant slowing of refrigerant flow causes a tenden-
cy for the discharge temperature to rise.
Refer to the following page(s). [8-8 Troubleshooting
LEV Problems]
13.
LEV9 malfunction
Not enough refrigerant is provided to the indoor or
outdoor unit due to high-low pressure bypass that re-
sults from the malfunction of LEV9.
Refer to the following page(s). [8-8 Troubleshooting
LEV Problems]
14
LEV4 malfunction
Refrigerant flood-back occurs when LEV4 is open
due to a malfunction, resulting in an excessively low
discharge temperature. When the valve is closed
during Heating operation (especially at low outside
temperature), compressor frequency does not accel-
erate properly.
Refer to the following page(s). [8-8 Troubleshooting
LEV Problems]
15.
Open phase in the power-supply due to improper
power-supply wiring
Make sure that the power-supply wiring is properly
connected. (Refer to item (5) in section [6-1 Read
before Test Run].)
Possible open phase.
Содержание PUHY-HP120TNU-A
Страница 1: ......
Страница 11: ...HWE18240_GB ...
Страница 27: ...HWE18240_GB ...
Страница 59: ...HWE18240_GB ...
Страница 69: ...HWE18240_GB ...
Страница 87: ...HWE18240_GB ...
Страница 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Страница 111: ...HWE18240_GB ...
Страница 120: ...HWE18240_GB 7 9 7 Error Code 7111 70 7 9 8 Error Code 7113 71 7 9 9 Error Code 7117 72 7 9 10 Error Code 7130 73 ...
Страница 121: ...HWE18240_GB ...
Страница 195: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 74 chapter 7 HWE18240_GB 7 Troubleshooting Using Error Codes ...
Страница 279: ...HWE18240_GB ...
Страница 297: ...HWE18240_GB ...
Страница 323: ... 10 2 LED Status Indicators Table 10 LED Status Indicators on the Outdoor Unit Circuit Board 26 chapter 10 HWE18240_GB ...
Страница 324: ......