[2-3 Switch Settings ]
HWE18240_GB
chapter 2 -
3
2 Restrictions
2) Remote controller wiring
*1 MA remote controller refers to MA remote controller (PAR-20MAU, PAR-21MAAU, PAR-30MAAU), MA simple re-
mote controller, and wireless remote controller.
*2 ME remote controller refers to ME remote controller, Compact ME remote controller, and LOSSNAY remote control-
ler.
*3 The use of cables that are smaller than 0.75mm
2
(AWG18) is recommended for easy handling.
*4 When connected to the terminal block on the Simple remote controller, use cables that meet the cable size specifi-
cations shown in the parenthesis.
*5 When connecting PAR-30MAAU or MA Simple remote controller, use sheathed cables with a minimum thickness of
0.3 mm
2
.
2-3
Switch Settings
1. Switch setting
The necessary switch settings depend on system configuration. Before performing wiring work, refer to the following page(s).
[2-7 Example System with an MA Remote Controller]
[2-8 Example System with an ME Remote Controller]
[2-9 Example System with an MA and an ME Remote Controller]
If the switch settings are changed while the unit is being powered, those changes will not take effect, and the unit will not
function properly.
*1. Applicable when LOSSNAY units are connected to the indoor-outdoor transmission line.
*2. The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2 in the order of
capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
*3. Turn off the power to all the outdoor units in the same refrigerant circuit.
*4. When setting the switch SW4 of the control board, set it with the outdoor unit power on. Refer to the following page(s).
[5-1-1 Outdoor Unit Switch Functions and Factory Settings]
MA remote controller
*1
ME remote controller
*2
Cable type
Type
VCTF, VCTFK, CVV, CVS, VVR, VVF, VCT Shielded cables CVVS, CPEVS, and MVVS
Number of
cores
2-core cable
2-core cable
Cable size
0.3 to 1.25mm
2 *3 *5
[AWG22 to 16]
0.3 to 1.25mm
2 *3
[AWG22 to 16]
(0.75 to 1.25mm
2
)
*4
[AWG18 to 16]
Maximum overall line
length
200 m [656ft] max.
The section of the cable that exceeds 10m
[32ft] must be included in the maximum in-
door-outdoor transmission line distance.
Units on which to set the switches
Symbol
Units to which the power must be shut off
CITY MULTI indoor unit
Main/sub unit
IC
Outdoor units
*3
and Indoor units
LOSSNAY, OA processing unit
*1
LC
Outdoor units
*3
and LOSSNAY
ATW
Water Hex Unit
AU
Outdoor units and Water Hex Unit
Air handling kit
IC
Outdoor units
*3
or field supplied air handling
unit
ME remote controller
Main/sub remote
controller
RC
Outdoor units
*3
MA remote controller
*4
Main/sub remote
controller
MA
Indoor units
CITY MULTI outdoor unit
*2
OC,OS1,OS2
Outdoor units
*3 *5
Содержание PUHY-HP120TNU-A
Страница 1: ......
Страница 11: ...HWE18240_GB ...
Страница 27: ...HWE18240_GB ...
Страница 59: ...HWE18240_GB ...
Страница 69: ...HWE18240_GB ...
Страница 87: ...HWE18240_GB ...
Страница 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Страница 111: ...HWE18240_GB ...
Страница 120: ...HWE18240_GB 7 9 7 Error Code 7111 70 7 9 8 Error Code 7113 71 7 9 9 Error Code 7117 72 7 9 10 Error Code 7130 73 ...
Страница 121: ...HWE18240_GB ...
Страница 195: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 74 chapter 7 HWE18240_GB 7 Troubleshooting Using Error Codes ...
Страница 279: ...HWE18240_GB ...
Страница 297: ...HWE18240_GB ...
Страница 323: ... 10 2 LED Status Indicators Table 10 LED Status Indicators on the Outdoor Unit Circuit Board 26 chapter 10 HWE18240_GB ...
Страница 324: ......