[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
HWE18240_GB
chapter 7 -
31
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
7-6-19
Error Codes [4240, 4245, 4246]
1. Error code definition
Overload protection (YNU)
2. Error definition and error detection method
If the output current of "(Iac) >Imax (Arms)" or "THHS > TOL" is continuously detected for 10 minutes during inverter operation.
Refer to the following page(s). [7-1 Error Code and Preliminary Error Code Lists]
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems]
7-6-20
Error Codes [4240, 4245, 4246]
1. Error code definition
Overload protection (TNU)
2. Error definition and error detection method
If the output current of "(Iac) >Imax (Arms)" or "THHS > TOL" is continuously detected for 10 minutes during inverter operation.
Refer to the following page(s). [7-1 Error Code and Preliminary Error Code Lists]
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems]
Cause
Check method and remedy
(1)
IPM contact failure
Check the IPM and cooling plate for proper contact. (Remove the inverter board,
and check the IPM heatsink grease.)
(2)
Air passage blockage
Check that the heat sink cooling air passage is not blocked
(3)
Power supply environment
Power supply voltage is 414 V or above.
(4)
Inverter, FAN board failure
Refer to the following page(s). [8-9 Troubleshooting Inverter Problems]
(5)
Compressor failure
Check that the compressor has not overheated during operation.
ĺ
Check the refrigerant circuit (oil return section).
Refer to the following page(s). [8-9-3 Checking the Compressor for Ground Fault
and Coil Resistance Problems]
(6)
The model selection switches
(SW5-3 - 5-8) on the outdoor
unit are set incorrectly.
Check the setting for the model selection switch on the outdoor unit (Dipswitches
SW5-3 - 5-8 on the outdoor unit control board).
For switch settings, refer to the following page(s). [7-9-2 Error Code [7101]]
Cause
Check method and remedy
(1)
IPM contact failure
Check the IPM and cooling plate for proper contact. (Remove the inverter board,
and check the IPM heatsink grease.)
(2)
Air passage blockage
Check that the heat sink cooling air passage is not blocked
(3)
Power supply environment
Power supply voltage is 188 V or above.
(4)
Inverter, FAN board failure
Refer to the following page(s). [8-9 Troubleshooting Inverter Problems]
(5)
Compressor failure
Check that the compressor has not overheated during operation.
ĺ
Check the refrigerant circuit (oil return section).
Refer to the following page(s). [8-9-3 Checking the Compressor for Ground Fault
and Coil Resistance Problems]
(6)
The model selection switches
(SW5-3 - 5-8) on the outdoor
unit are set incorrectly.
Check the setting for the model selection switch on the outdoor unit (Dipswitches
SW5-3 - 5-8 on the outdoor unit control board).
For switch settings, refer to the following page(s). [7-9-2 Error Code [7101]]
Содержание PUHY-HP120TNU-A
Страница 1: ......
Страница 11: ...HWE18240_GB ...
Страница 27: ...HWE18240_GB ...
Страница 59: ...HWE18240_GB ...
Страница 69: ...HWE18240_GB ...
Страница 87: ...HWE18240_GB ...
Страница 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Страница 111: ...HWE18240_GB ...
Страница 120: ...HWE18240_GB 7 9 7 Error Code 7111 70 7 9 8 Error Code 7113 71 7 9 9 Error Code 7117 72 7 9 10 Error Code 7130 73 ...
Страница 121: ...HWE18240_GB ...
Страница 195: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 74 chapter 7 HWE18240_GB 7 Troubleshooting Using Error Codes ...
Страница 279: ...HWE18240_GB ...
Страница 297: ...HWE18240_GB ...
Страница 323: ... 10 2 LED Status Indicators Table 10 LED Status Indicators on the Outdoor Unit Circuit Board 26 chapter 10 HWE18240_GB ...
Страница 324: ......