Error Code [6846]
1. Error code definition
Start-up time over
2. Error definition and error detection method
Start-up time over The unit cannot finish start-up process within 4 minutes after power on.
3. Cause, check method and remedy
Note: Refer also to the Service Handbook for the indoor units.
Cause
Check method and remedy
(1)
Contact failure of indoor/outdoor unit connecting wire
Check disconnection or looseness or polarity
of indoor/outdoor unit connecting wire of in-
door and outdoor units.
(2)
Diameter or length of indoor/outdoor unit connecting wire is out
of specified capacity.
Check the following: Diameter of the cables
used for indoor-outdoor lines; maximum line
distance between indoor and outdoor units
(max. 50 m); maximum line distance be-
tween indoor units (daisy-changed cables)
(max. 30 m); and if flat cables such as VVF is
used, make sure they are connected in the
order of S1, S2, and S3.
(3)
2 or more outdoor units have refrigerant address "0". (In case of
group control)
When units are controlled as groups, check
the refrigerant address (SW1 (3-6) on the
outdoor unit control board settings) for dupli-
cates.
(4)
Noise has entered into power supply or indoor/outdoor unit con-
necting wire.
Check the transmission lines for problems.
Содержание PUHY-HP120TNU-A
Страница 1: ......
Страница 11: ...HWE18240_GB ...
Страница 27: ...HWE18240_GB ...
Страница 59: ...HWE18240_GB ...
Страница 69: ...HWE18240_GB ...
Страница 87: ...HWE18240_GB ...
Страница 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Страница 111: ...HWE18240_GB ...
Страница 120: ...HWE18240_GB 7 9 7 Error Code 7111 70 7 9 8 Error Code 7113 71 7 9 9 Error Code 7117 72 7 9 10 Error Code 7130 73 ...
Страница 121: ...HWE18240_GB ...
Страница 195: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 74 chapter 7 HWE18240_GB 7 Troubleshooting Using Error Codes ...
Страница 279: ...HWE18240_GB ...
Страница 297: ...HWE18240_GB ...
Страница 323: ... 10 2 LED Status Indicators Table 10 LED Status Indicators on the Outdoor Unit Circuit Board 26 chapter 10 HWE18240_GB ...
Страница 324: ......