[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
22
-
chapter 7
HWE18240_GB
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
7-6-2
Error Code [4106]
1. Error code definition
<Transmission power supply fault Error detail code FF (Outdoor unit)>
2. Error definition and error detection method
Transmission power output failure
3. Cause
1) Wiring failure
2) Transmission power supply cannot output voltage because overcurrent was detected.
3) Voltage cannot be output due to transmission power supply problem.
4) Transmission voltage detection circuit failure
4. Check method and remedy
Check the transmission power supply circuit on all outdoor units in a given refrigerant circuit for problems. [8-10-2 Trouble-
shooting Problems with Outdoor Unit Transmission Power Supply Circuit]
1. Error code definition
<Transmission power supply fault other than error detail code FF (Outdoor unit)>
2.Error definition and error detection method
Transmission power reception failure
3.Cause
One of the outdoor units stopped supplying power, but no other outdoor units start supplying power.
4.Check method and remedy
Check the transmission power supply circuit on all outdoor units in a given refrigerant circuit for problems. [8-10-2 Trouble-
shooting Problems with Outdoor Unit Transmission Power Supply Circuit]
7-6-3
Error Code [4109]
1. Error code definition
Indoor unit fan operation error
2. Error definition and error detection method
1) Connector CN28 has remained open-circuited for 100 consecutive secondsduring operation.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Auxiliary relay fault
The coil or the wiring of the auxiliary relay connected to
CN28 is faulty.
(2)
Connector (CN28) is disconnected.
Check the connector for proper connection.
(3)
Blown fuse
Check the fuse on the control circuit board.
(4)
Motor error (thermistor error inside the motor)
Check the unit fan for proper operation in the test run
mode.
If no problems are found with items 1 through 3 above and
the fan does not operate, replace the motor.
Содержание PUHY-HP120TNU-A
Страница 1: ......
Страница 11: ...HWE18240_GB ...
Страница 27: ...HWE18240_GB ...
Страница 59: ...HWE18240_GB ...
Страница 69: ...HWE18240_GB ...
Страница 87: ...HWE18240_GB ...
Страница 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Страница 111: ...HWE18240_GB ...
Страница 120: ...HWE18240_GB 7 9 7 Error Code 7111 70 7 9 8 Error Code 7113 71 7 9 9 Error Code 7117 72 7 9 10 Error Code 7130 73 ...
Страница 121: ...HWE18240_GB ...
Страница 195: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 74 chapter 7 HWE18240_GB 7 Troubleshooting Using Error Codes ...
Страница 279: ...HWE18240_GB ...
Страница 297: ...HWE18240_GB ...
Страница 323: ... 10 2 LED Status Indicators Table 10 LED Status Indicators on the Outdoor Unit Circuit Board 26 chapter 10 HWE18240_GB ...
Страница 324: ......