[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
HWE18240_GB
chapter 7 -
29
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
7-6-14
Error Code [4220] Detail Code 129
1. Error code definition
Control power supply error (Detail code 129)(outdoor unit)
2. Error definition and error detection method
INV42Y and INV38
Detection of insufficient drive voltage for relays on INV board
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems]
7-6-15
Error Codes [4220, 4225, 4226] Detail Code 131
1. Error code definition
Low bus voltage at startup (Detail code 131) (YNU)
2. Error definition and error detection method
When Vdc
289 V is detected just before the inverter operation. (YNU)
3. Cause, check method and remedy
(1) Inverter main circuit failure
Same as detail code 108 of 4220 error
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems]
7-6-16
Error Codes [4220, 4225, 4226] Detail Code 131
1. Error code definition
Low bus voltage at startup (Detail code 131) (TNU)
2. Error definition and error detection method
When Vdc
160 V is detected just before the inverter operation. (TNU)
3. Cause, check method and remedy
(1) Inverter main circuit failure
Same as detail code 108 of 4220 error
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems]
Cause
Check method and remedy
(1)
Contact failure
<INV42Y and INV38>
Check the connectors CNRY on INV board and CNRYA on MAIN board for proper
connections.
(2)
Voltage check
Disconnect the connector CNRYA from the control board and check the voltage at
the connector CNRYA. If a voltage of 13 V is not output, replace the control board
and the PS board.
(3)
Inverter board failure
If the problem persists after reboot, replace the INV board.
Содержание PUHY-HP120TNU-A
Страница 1: ......
Страница 11: ...HWE18240_GB ...
Страница 27: ...HWE18240_GB ...
Страница 59: ...HWE18240_GB ...
Страница 69: ...HWE18240_GB ...
Страница 87: ...HWE18240_GB ...
Страница 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Страница 111: ...HWE18240_GB ...
Страница 120: ...HWE18240_GB 7 9 7 Error Code 7111 70 7 9 8 Error Code 7113 71 7 9 9 Error Code 7117 72 7 9 10 Error Code 7130 73 ...
Страница 121: ...HWE18240_GB ...
Страница 195: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 74 chapter 7 HWE18240_GB 7 Troubleshooting Using Error Codes ...
Страница 279: ...HWE18240_GB ...
Страница 297: ...HWE18240_GB ...
Страница 323: ... 10 2 LED Status Indicators Table 10 LED Status Indicators on the Outdoor Unit Circuit Board 26 chapter 10 HWE18240_GB ...
Страница 324: ......