[7-9 Error Code Definitions and Solutions: Codes [7000 - 7999] ]
HWE18240_GB
chapter 7 -
71
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
7-9-8
Error Code [7113]
1. Error code definition
Function setting error (improper connection of CNTYP)
2. Error source, cause, check method and remedy
Error source
Cause
Check method and remedy
Outdoor unit
(1)
Wiring fault
(Detail code 15)
(2)
Loose connectors, short-cir-
cuit, contact failure
1)
Check the connector CNTYP5 on the control board for proper con-
nection.
2)
Check the connector CNTYP4 on the control board for proper con-
nection.
(Detail code 14)
(3)
Incompatible control board
and INV board (replacement
with a wrong circuit board)
1)
Check the settings of SW5-3 through SW5-6 on the control board.
(4)
DIP SW setting error on the
control board
2)
Check the connector CNTYP4 on the control board for proper con-
nection.
(Detail code 12)
1)
Check the settings of SW5-3 through SW5-6 on the control board.
2)
Check the connector CNTYP2 on the control board for proper con-
nection.
3)
Check the connector CNTYP5 on the control board for proper con-
nection.
4)
Check the connector CNTYP on the INV board for proper connec-
tion.
(Detail code 16)
1)
Check the settings of SW5-3 through SW5-6 on the control board.
2)
Check the connector CNTYP5 on the control board for proper con-
nection.
3)
Check the connector CNTYP2 on the control board for proper con-
nection.
4)
Check the wiring between the control board and INV board.
Refer to the following page(s). [7-2-1 Error Code [0403]]
5)
Check the connector CNTYP on the INV board for proper connec-
tion.
(Detail codes 56, 66)
1)
Check the settings of SW5-3 through SW5-6 on the control board.
2)
Check the wiring between the control board and the Fan INV board.
Refer to the following page(s). [7-2-1 Error Code [0403]]
3)
Make sure the FAN INV board has been properly replaced.
(Detail code 0, 1, 5, 6)
1)
Check the wiring between the control board and INV board.
Refer to the following page(s). [7-2-1 Error Code [0403]]
2)
Check the settings of SW5-3 through SW5-6 on the control board.
3)
Check the connector CNTYP5 on the control board for proper con-
nection.
(Detail code Miscellaneous)
*If a set-model-name identification error occurs, check the detail code
on the unit on which the error occurred. The detail code that appears
on other units will be different from the ones shown above.
Содержание PUHY-HP120TNU-A
Страница 1: ......
Страница 11: ...HWE18240_GB ...
Страница 27: ...HWE18240_GB ...
Страница 59: ...HWE18240_GB ...
Страница 69: ...HWE18240_GB ...
Страница 87: ...HWE18240_GB ...
Страница 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Страница 111: ...HWE18240_GB ...
Страница 120: ...HWE18240_GB 7 9 7 Error Code 7111 70 7 9 8 Error Code 7113 71 7 9 9 Error Code 7117 72 7 9 10 Error Code 7130 73 ...
Страница 121: ...HWE18240_GB ...
Страница 195: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 74 chapter 7 HWE18240_GB 7 Troubleshooting Using Error Codes ...
Страница 279: ...HWE18240_GB ...
Страница 297: ...HWE18240_GB ...
Страница 323: ... 10 2 LED Status Indicators Table 10 LED Status Indicators on the Outdoor Unit Circuit Board 26 chapter 10 HWE18240_GB ...
Страница 324: ......