[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
HWE18240_GB
chapter 7 -
23
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
7-6-4
Error Code [4114]
1. Error code definition
Indoor unit fan motor error
2. Error definition and error detection method
When the fan motor output from the indoor unit circuit board is ON and when the rotation speed input from the fan motor cannot
be detected for 30 seconds or more
3. Cause, check method and remedy
7-6-5
Error Code [4116]
1. Error code definition
RPM error/Motor error
2. Error definition and error detection method
LOSSNAY
The motor keep running even if the power is OFF.
The thermal overload relay is ON. (Only for the three-phase model)
Indoor unit
If detected less than 180rpm or more than 2000rpm, the indoor unit will restart and keep running for 3 minutes.If detected
again, the display will appear.
3. Cause, check method and remedy
7-6-6
Error Code [4121]
1. Error code definition
Function setting error
2. Error source, cause, check method and remedy
Cause
Check method and remedy
(1)
Fan motor connector contact failure
Check the fan motor connector CNMF for proper connection.
(2)
Indoor unit circuit board failure
Remove the fan motor connector CNMF and check the voltage at the
indoor unit circuit board.
Testing point 1. 280 VDC (Between CNMF1 (+) and CNMF4 (-))
2. 15 VDC (Between CNMF5 (+) and CNMF4 (-))
Replace the indoor unit circuit board if the voltage is abnormal.
If the 4114 error persists after the indoor unit circuit board is replaced,
replace the fan motor as well.
(3)
Fan motor fault
Replace the fan motor if the voltage is normal in step (2) above.
If the 4114 error persists after the fan motor is replaced, replace the in-
door unit circuit board as well.
Cause
Check method and remedy
(1)
Board failure
Replace the board.
(2)
Motor malfunction
Check for the motor and the solenoid switch.
(3)
Solenoid switch malfunction
Error source
Cause
Check method and remedy
Outdoor unit
(1) Dip switch setting error on the control board
Check the SW6-1 setting on the control board
(2) Connector connection error on the control
board
Check that nothing is connected to the connector
CNAF on the control board.
(3) Control board failure
Replace the control board if no problems are
found with the two items above.
Содержание PUHY-HP120TNU-A
Страница 1: ......
Страница 11: ...HWE18240_GB ...
Страница 27: ...HWE18240_GB ...
Страница 59: ...HWE18240_GB ...
Страница 69: ...HWE18240_GB ...
Страница 87: ...HWE18240_GB ...
Страница 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Страница 111: ...HWE18240_GB ...
Страница 120: ...HWE18240_GB 7 9 7 Error Code 7111 70 7 9 8 Error Code 7113 71 7 9 9 Error Code 7117 72 7 9 10 Error Code 7130 73 ...
Страница 121: ...HWE18240_GB ...
Страница 195: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 74 chapter 7 HWE18240_GB 7 Troubleshooting Using Error Codes ...
Страница 279: ...HWE18240_GB ...
Страница 297: ...HWE18240_GB ...
Страница 323: ... 10 2 LED Status Indicators Table 10 LED Status Indicators on the Outdoor Unit Circuit Board 26 chapter 10 HWE18240_GB ...
Страница 324: ......