[7-7 Error Code Definitions and Solutions: Codes [5000 - 5999] ]
44
-
chapter 7
HWE18240_GB
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
7-7-11
Error Codes [5305, 5306] Detail Code 135
1. Error code definition
Current sensor fault (Detail code 135)
2. Error definition and error detection method
Detection of output current below 0.2 Arms for 10 continuous seconds while fan motor is in operation
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems]
7-7-12
Error Codes [5305, 5306] Detail Code 136
1. Error code definition
Current sensor/circuit fault (Detail code 136)
2. Error definition and error detection method
Detection of abnormal value by the current detection circuit before the startup of fan motor
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems]
7-7-13
Error Code [5701]
1. Error code definition
Loose float switch connector
2. Error definition and error detection method
Detection of the disconnected float switch (open-phase condition) during operation
3. Cause, check method and remedy
(1) CN4F disconnection or contact failure
Check for disconnection of the connector (CN4F) on the indoor unit control board.
Cause
Check method and remedy
(1)
Open output phase of fan board
Check the output wiring from the fan board for proper con-
nection.
(2)
Fan motor error
Refer to the following page(s).
[8-9-7 Checking the Fan Motor for Ground Fault and Coil Re-
sistance Problems]
(3)
Fan board failure
Refer to the following page(s).
[8-9-8 Checking the Fan Board Error Detection Circuit at No
Load]
[8-9-9 Checking the Fan Board for Damage at No Load]
[8-9-10 Checking the Fan Board for Damage with Load]
Cause
Check method and remedy
(1)
Fan board fault
Refer to the following page(s).
[8-9-8 Checking the Fan Board Error Detection Circuit at No
Load]
[8-9-9 Checking the Fan Board for Damage at No Load]
[8-9-10 Checking the Fan Board for Damage with Load]
Содержание PUHY-HP120TNU-A
Страница 1: ......
Страница 11: ...HWE18240_GB ...
Страница 27: ...HWE18240_GB ...
Страница 59: ...HWE18240_GB ...
Страница 69: ...HWE18240_GB ...
Страница 87: ...HWE18240_GB ...
Страница 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Страница 111: ...HWE18240_GB ...
Страница 120: ...HWE18240_GB 7 9 7 Error Code 7111 70 7 9 8 Error Code 7113 71 7 9 9 Error Code 7117 72 7 9 10 Error Code 7130 73 ...
Страница 121: ...HWE18240_GB ...
Страница 195: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 74 chapter 7 HWE18240_GB 7 Troubleshooting Using Error Codes ...
Страница 279: ...HWE18240_GB ...
Страница 297: ...HWE18240_GB ...
Страница 323: ... 10 2 LED Status Indicators Table 10 LED Status Indicators on the Outdoor Unit Circuit Board 26 chapter 10 HWE18240_GB ...
Страница 324: ......