[5-1 Dipswitch Functions and Factory Settings ]
2
-
chapter 5
HWE18240_GB
5 Control
SW7
1
Enables or disables the de-
tection of the following
types of inverter compres-
sor errors
ACCT, DCCT sensor er-
ror(5301 Detail code 115,
116)
ACCT, DCCT sensor cir-
cuit error(5301 Detail code
117, 118)
IPM open-phase/CNCT2
connection error(5301 De-
tail code 119)
Wiring connection er-
ror(5301 Detail code 120)
Error detection
enabled
Error detection
disabled (no-load
operation al-
lowed)
Any time after power
on
C
2
Enables or disables no-
load operation of the left
fan inverter
The unit continues no-load
operation for 30 seconds
and comes to an error
stop. See the relevant pag-
es for details: [8-9-8
Checking the Fan Board
for Damage at No Load]
No-load opera-
tion disabled
No-load opera-
tion enabled
Any time after power
on
C
3
-
4
Enables or disables no-
load operation of the right
fan inverter
The unit continues no-load
operation for 30 seconds
and comes to an error
stop. See the relevant pag-
es for details: [8-9-8
Checking the Fan Board
for Damage at No Load]
No-load opera-
tion disabled
No-load opera-
tion enabled
Any time after power
on
C
5
-
-
-
-
-
6
-
-
-
-
-
7
-
-
-
-
-
8
-
-
-
-
-
9
Switches between the nor-
mal startup mode and the
USB writer rewrite mode
Normal startup
mode
USB writer re-
write mode
Before power on
C
Switch
Function
Function according to switch setting
Switch setting timing
Units that require
switch setting
(Note 2)
OFF
ON
Содержание PUHY-HP120TNU-A
Страница 1: ......
Страница 11: ...HWE18240_GB ...
Страница 27: ...HWE18240_GB ...
Страница 59: ...HWE18240_GB ...
Страница 69: ...HWE18240_GB ...
Страница 87: ...HWE18240_GB ...
Страница 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Страница 111: ...HWE18240_GB ...
Страница 120: ...HWE18240_GB 7 9 7 Error Code 7111 70 7 9 8 Error Code 7113 71 7 9 9 Error Code 7117 72 7 9 10 Error Code 7130 73 ...
Страница 121: ...HWE18240_GB ...
Страница 195: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 74 chapter 7 HWE18240_GB 7 Troubleshooting Using Error Codes ...
Страница 279: ...HWE18240_GB ...
Страница 297: ...HWE18240_GB ...
Страница 323: ... 10 2 LED Status Indicators Table 10 LED Status Indicators on the Outdoor Unit Circuit Board 26 chapter 10 HWE18240_GB ...
Страница 324: ......