[2-4 M-NET Address Settings ]
6
-
chapter 2
HWE18240_GB
2 Restrictions
2-4-5
Start/Stop Control of Indoor Units
Each indoor unit (or group of indoor units) can be controlled individually by setting SW 1-9 and 1-10.
*1. Do not shut off power to the outdoor units. Doing so will cut off the power supply to the compressors and the heater on
the outdoor units and may result in compressor malfunction when operation is restored after a power failure.
*2. Not applicable to units with a built-in drain pump or humidifier.
*3. Models with a built-in drain pump cannot be turned on/off by the plug individually. All the units in the same refrigerant cir-
cuits will be turned on or off by the plug.
*4. Requires that the dipswitch settings for all the units in the group be made.
*5. To control the external input to and output from the air conditioners with the PLC software for general equipment via the
AE-200,AG-150A, GB-50ADA, or G(B)-50A, set SW1-9 and SW1-10 to ON. With these settings made, the power start-
stop function becomes disabled. To use the auto recovery function after power failure while these settings are made, set
SW1-5 to ON.
2-4-6
Miscellaneous Settings
Cooling-only setting for the indoor unit: Cooling only model (Factory setting: SW3-1 "OFF.")
When using indoor unit as a cooling-only unit, set SW3-1 to ON.
Function
Operation of the indoor unit when the operation is resumed after the unit was
stopped
Setting (SW1)
*4 *5
9
10
Power ON/OFF by
the plug
*1,*2,*3
Indoor unit will go into operation regardless of its operation status before power
off (power failure). (In approx. 5 minutes)
OFF
ON
Automatic restoration
after power failure
Indoor unit will go into operation if it was in operation when the power was
turned off (or cut off due to power failure). (In approx. 5 minutes)
ON
OFF
Indoor unit will remain stopped regardless of its operation status before power
off (power failure).
OFF
OFF
Содержание PUHY-HP120TNU-A
Страница 1: ......
Страница 11: ...HWE18240_GB ...
Страница 27: ...HWE18240_GB ...
Страница 59: ...HWE18240_GB ...
Страница 69: ...HWE18240_GB ...
Страница 87: ...HWE18240_GB ...
Страница 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Страница 111: ...HWE18240_GB ...
Страница 120: ...HWE18240_GB 7 9 7 Error Code 7111 70 7 9 8 Error Code 7113 71 7 9 9 Error Code 7117 72 7 9 10 Error Code 7130 73 ...
Страница 121: ...HWE18240_GB ...
Страница 195: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 74 chapter 7 HWE18240_GB 7 Troubleshooting Using Error Codes ...
Страница 279: ...HWE18240_GB ...
Страница 297: ...HWE18240_GB ...
Страница 323: ... 10 2 LED Status Indicators Table 10 LED Status Indicators on the Outdoor Unit Circuit Board 26 chapter 10 HWE18240_GB ...
Страница 324: ......