[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
36
-
chapter 7
HWE18240_GB
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
7-6-25
Error Code [4250] Detail Codes 121, 128, and 122
1. Error code definition
DCL overcurrent error (H/W) (Detail code 121 and 128)(outdoor unit) DCL overcurrent error (S/W) (Detail code 122)
(outdoor unit)
2. Error definition and error detection method
When a DCL overcurrent is detected by the electric current sensor
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems]
7-6-26
Error Codes [4255, 4256] Detail Code 137
1. Error code definition
Motor synchronization loss (Detail code 137)
2. Error definition and error detection method
Fan motor locking was detected during operation.
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems]
Cause
Check method and remedy
(1)
Inverter-output-related
items
Refer to the following page(s). [8-9-2 Checking the Inverter Board Error Detection
Circuit]
Refer to the following page(s). [8-9-3 Checking the Compressor for Ground Fault
and Coil Resistance Problems]
Refer to the following page(s). [8-9-4 Checking the Inverter for Damage at No-Load]
Refer to the following page(s). [8-9-5 Checking the Inverter for Damage during Com-
pressor Operation]
Refer to the following page(s). [8-9-11 Checking the Installation Conditions]
Cause
Check method and remedy
(1)
Fan motor locking
Check the fan blades for objects obstructing fan rotation.
(2)
Fan motor failure
Refer to the following page(s).
[8-9-7 Checking the Fan Motor for Ground Fault and Coil Re-
sistance Problems]
(3)
Fan board failure
Refer to the following page(s).
[8-9-8 Checking the Fan Board Error Detection Circuit at No
Load]
[8-9-9 Checking the Fan Board for Damage at No Load]
[8-9-10 Checking the Fan Board for Damage with Load]
Содержание PUHY-HP120TNU-A
Страница 1: ......
Страница 11: ...HWE18240_GB ...
Страница 27: ...HWE18240_GB ...
Страница 59: ...HWE18240_GB ...
Страница 69: ...HWE18240_GB ...
Страница 87: ...HWE18240_GB ...
Страница 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Страница 111: ...HWE18240_GB ...
Страница 120: ...HWE18240_GB 7 9 7 Error Code 7111 70 7 9 8 Error Code 7113 71 7 9 9 Error Code 7117 72 7 9 10 Error Code 7130 73 ...
Страница 121: ...HWE18240_GB ...
Страница 195: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 74 chapter 7 HWE18240_GB 7 Troubleshooting Using Error Codes ...
Страница 279: ...HWE18240_GB ...
Страница 297: ...HWE18240_GB ...
Страница 323: ... 10 2 LED Status Indicators Table 10 LED Status Indicators on the Outdoor Unit Circuit Board 26 chapter 10 HWE18240_GB ...
Страница 324: ......