[8-9 Troubleshooting Inverter Problems ]
HWE18240_GB
chapter 8 -
35
8 Troubleshooting Based on Observed Symptoms
8-9-7
Checking the Fan Board Error Detection Circuit at No Load
8-9-8
Checking the Fan Board for Damage at No Load
Items to be checked
Phenomena
Remedy
(1)
Stop the unit.
Turn off the breaker.
*Be sure to turn off the power.
1)
An error other than current sensor er-
ror (5305, 5306: Detail code 135) is
detected during operation.
Replace the fan board.
(2)
Disconnect the output wiring
to the fan motor.
Disconnect connector
RYFAN1. (On a model with
two fan motors, RYFAN1 cor-
responds to the right fan and
RYFAN2 corresponds to the
left fan (when seen from the
front).)
2)
Current sensor fault
Error code: 5305, 5306
Detail code: 135
Normal
*When done checking, reconnect all
connectors as they were. Unless
they are properly reconnected, cur-
rent sensor fault will not be resolved.
(3)
Turn on the breaker.
(4)
Operate the unit.
Items to be checked
Phenomena
Remedy
(1)
Stop the unit.
Turn off the breaker.
*Be sure to turn off the power.
1)
An error other than the current sen-
sor error (5305, 5306 Detail code
135) is detected within 30 seconds
from the startup of operation.
Replace the fan board.
(2)
To allow for the disconnection
of output wiring from the fan
motor, disconnect connector
RYFAN1. (On a model with
two fan motors, RYFAN1 cor-
responds to the right fan and
RYFAN2 corresponds to the
left fan (when seen from the
front).)
2)
Inter-wire voltage imbalance of 5 V or
above
Replace the fan board.
(3)
Set SW7-2 on the control
board to ON. On a model with
two fan motors, set SW7-2
(left fan when seen from the
front) or SW7-4 (right fan
when seen from the front) to
ON.
3)
No inter-wire voltage imbalance ex-
ists. A current sensor error (Detail
code 135) is detected 30 seconds af-
ter the startup of operation, and the
operation stops.
Normal
*When done checking, reconnect all
connectors as they were. Unless
they are properly reconnected, cur-
rent sensor fault will not be resolved.
(4)
Turn on the breaker.
(5)
Operate the unit
Содержание PUHY-HP120TNU-A
Страница 1: ......
Страница 11: ...HWE18240_GB ...
Страница 27: ...HWE18240_GB ...
Страница 59: ...HWE18240_GB ...
Страница 69: ...HWE18240_GB ...
Страница 87: ...HWE18240_GB ...
Страница 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Страница 111: ...HWE18240_GB ...
Страница 120: ...HWE18240_GB 7 9 7 Error Code 7111 70 7 9 8 Error Code 7113 71 7 9 9 Error Code 7117 72 7 9 10 Error Code 7130 73 ...
Страница 121: ...HWE18240_GB ...
Страница 195: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 74 chapter 7 HWE18240_GB 7 Troubleshooting Using Error Codes ...
Страница 279: ...HWE18240_GB ...
Страница 297: ...HWE18240_GB ...
Страница 323: ... 10 2 LED Status Indicators Table 10 LED Status Indicators on the Outdoor Unit Circuit Board 26 chapter 10 HWE18240_GB ...
Страница 324: ......