[7-3 Error Code Definitions and Solutions: Codes [1000 - 1999] ]
HWE18240_GB
chapter 7 -
11
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
7-3-4
Error Code [1302] (at startup)
1. Error code definition
High pressure fault 2 (Outdoor unit)
2. Error definition and error detection method
If the pressure of 0.098MPa [14psi] or lower is registered on the pressure sensor immediately before start-up, it will trigger an
abnormal stop, and error code "1302" will be displayed.
3. Cause, check method and remedy
7-3-5
Error Code [1500]
1. Error code definition
Refrigerant overcharge
2. Error definition and error detection method
An error can be detected by the discharge temperature superheat.
1) If the formula "ToilSH (shell bottom SH)
10°C [50°F]" is satisfied during operation (first detection), the outdoor unit stops,
goes into the 3-minute restart mode, and starts up in three minutes.
2) If the formula "TdSH
10°C [50°F]" is satisfied again within 30 minutes of the fifth stoppage of the outdoor unit (sixth detec-
tion), the unit comes to an abnormal stop, and the error code "1500" appears.
3) If the formula "ToilSH (shell bottom SH)
10°C [50°F]" is satisfied 30 minutes or more after the first stoppage of the outdoor
unit, the same sequence as Item "1 above (first detection) is followed.
4) For 30 minutes after the stop of the outdoor unit, preliminary errors will be displayed on the LED display.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Inner pressure drop due to a leakage.
Refer to the following page(s). [8-5-1 Comparing the
High-Pressure Sensor Measurement and Gauge
Pressure]
(2)
Pressure sensor failure
(3)
Shorted-circuited pressure sensor cable due to torn
outer rubber
(4)
A pin on the male connector on the pressure sensor
is missing or contact failure
(5)
Disconnected pressure sensor cable
(6)
Failure of the pressure sensor input circuit on the
controller board
(7)
Open phase in the power-supply due to improper
power-supply wiring
Refer to item (5) in section [6-1 Read before Test
Run].
Cause
Check method and remedy
(1)
Overcharged refrigerant
Refer to the following page(s). [6-3 Evaluating and Adjust-
ing Refrigerant Charge]
(2)
Thermistor input circuit failure on the control board
Check the temperature and pressure readings on the sen-
sor that are displayed on the LED monitor.
(3)
Faulty mounting of thermistor (TH15)
Check the temperature and pressure readings on the
thermistor that are displayed on the LED monitor.
(4)
Outdoor unit LEV2 actuation failure -> Heating
Refer to the following page(s). [8-8 Troubleshooting LEV
Problems]
Содержание PUHY-HP120TNU-A
Страница 1: ......
Страница 11: ...HWE18240_GB ...
Страница 27: ...HWE18240_GB ...
Страница 59: ...HWE18240_GB ...
Страница 69: ...HWE18240_GB ...
Страница 87: ...HWE18240_GB ...
Страница 109: ... 5 2 Outdoor Unit Control 22 chapter 5 HWE18240_GB 5 Control ...
Страница 111: ...HWE18240_GB ...
Страница 120: ...HWE18240_GB 7 9 7 Error Code 7111 70 7 9 8 Error Code 7113 71 7 9 9 Error Code 7117 72 7 9 10 Error Code 7130 73 ...
Страница 121: ...HWE18240_GB ...
Страница 195: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 74 chapter 7 HWE18240_GB 7 Troubleshooting Using Error Codes ...
Страница 279: ...HWE18240_GB ...
Страница 297: ...HWE18240_GB ...
Страница 323: ... 10 2 LED Status Indicators Table 10 LED Status Indicators on the Outdoor Unit Circuit Board 26 chapter 10 HWE18240_GB ...
Страница 324: ......