(2) Removal procedure
The Ethernet adapter module can be removed from the DIN rail in reverse order of the mounting procedure.
(3) Applicable DIN rail models (IEC 60715)
• TH35-7.5Fe
• TH35-7.5Al
• TH35-15Fe
(4) DIN rail stopper
Use stoppers that can be attached to the DIN rail.
(5) Interval between DIN rail mounting screws
To ensure the strength of the DIN rail, tighten DIN rail mounting screws (sold separately) 30mm away from the
both edges of the DIN rail and at intervals of 200mm or less.
35mm
P=200mm or less
DIN rail
DIN rail mounting screw
(obtained by user)
P
P
P
30mm
or less
30mm
or less