222
(1) Diagnostic information
(2) Drive information
Number
Name
Description
Details
Set by
(Set timing)
SM0
Diagnostic error
OFF: No error
ON: Error
Turns on if an error is detected by the diagnostics.
Stays on even if it returns to normal.
S
(Error)
SM1
Self-diagnostic error
OFF: No self-diagnostic error
ON: Self-diagnostic error
Turns on if an error is detected by the self-diagnostics.
Stays on even if it returns to normal.
SM5
Common error
information
OFF: No common error
information
ON: Common error
information
Turns on if there is any common error information when SM0 turns on.
SM16
Individual error
information
OFF: No individual error
information
ON: Individual error
information
Turns on if there is any individual error information when SM0 turns on.
SM50
Error clear
OFF
ON: Error clear
Clears an error.
U
SM53
DC DOWN detection
OFF: No DC DOWN
ON: DC DOWN detected
Turns on if a momentary power failure of 10ms or less occurs. The
status is reset when power is turned on from off.
S
(Error)
Number
Name
Description
Details
Set by
(Set timing)
SM681
Parameter memory
writing flag
ON: Writing
OFF: Not writing
Turns on while writing parameters to a flash ROM, and turns off when
the writing is completed.
S
(Write)
SM682
Parameter memory
rewrite count error
flag
ON: Rewrite count reached
100000
OFF: Rewrite count less than
100000
Turns on when the count of rewriting parameters to a flash ROM
reaches 100000.
(The Ethernet adapter module needs to be replaced.)
Содержание NZ2GF-ETB
Страница 1: ...CC Link IE Field Network Ethernet Adapter Module User s Manual NZ2GF ETB ...
Страница 2: ......
Страница 49: ...47 CHAPTER 4 PROCEDURE BEFORE THE OPERATION 4 4 1 Start Up Procedure Memo ...
Страница 82: ...80 10 The following dialog box is displayed 11 Set the switch on the Ethernet adapter module to RUN Click ...
Страница 198: ...196 a Detail Setting ...
Страница 246: ...244 Memo ...
Страница 253: ......