171
CHAPTER 9 TROUBLESHOOTING
9
9.
5
Er
ror C
o
de List
(4) Error code list (D000
H
to DFFF
H
)
The following lists the error messages, error conditions, causes, and actions of the error codes (D000
H
to
DFFF
H
).
Error code
Error
Action
D038
H
No corresponding station (IP
communication test)
If the own station, target station, or relay station is disconnected from the
network, identify the cause of the disconnection and take action.
D039
H
IP packet transfer function not
supported (IP communication test)
Check the first five digits of the serial number of the module on the station on
the route next to the faulty station. If the module does not support the used
function, replace it with the module with the latest version.
D0A0
H
Transient data transmission response
wait timeout
• If the originating station or the target station is disconnected from the
network, identify the cause of the disconnection and take action.
• When the mode of the master station is "Online (High Speed Mode)",
change it to "Online (Normal Mode)" and retry the operation.
• When the receiving station encountered overloading of transient data,
reduce the frequency of transient transmission and then retry the
operation.
D0A1
H
Transient data transmission
completion wait timeout
• Check if the cables and switching hub are connected properly.
• Exchange the cables between PORT1 and PORT2 and retry the
operation.
• Reduce the frequency of transient transmission and then retry the
operation.
• Perform a unit test on the Ethernet adapter module. If the failure occurs
again, the hardware of the Ethernet adapter module may be faulty. Please
consult your local Mitsubishi representative.
D0A2
H
Transient data transmission
processing wait timeout
• Reduce the frequency of transient transmission and then retry the
operation.
• Check if the cable of the request source and the switching hub are
connected properly.
D0A3
H
Transient data transmission error
• If the originating station or the target station is disconnected from the
network, identify the cause of the disconnection and take action.
• Correct the target station number of the transient data, and retry the
operation.
D0A4
H
to D0A6
H
Transient transmission failed
• Check if the cables and the switching hub are connected properly.
• Exchange the cables between PORT1 and PORT2 and retry the
operation.
• Reduce the frequency of transient transmission and then retry the
operation.
• Perform a unit test on the Ethernet adapter module. If the failure occurs
again, the hardware of the Ethernet adapter module may be faulty. Please
consult your local Mitsubishi representative.
D0A7
H
Transient reception failed
D0E0
H
Station type mismatch
In Network Configuration Setting of the master station, change the station
type of the Ethernet adapter module to intelligent device station.
D0E1
H
Own station specified as reserved
• In Network Configuration Setting of the master station, cancel the reserved
station setting.
• Change the station number of the Ethernet adapter module to a station
number that is not reserved.
D0E2
H
Station No. duplication (own station)
• Change the station number so that it will not duplicated with any other
station number.
• After taking the above action, power off and then on all of the stations that
detected the station number duplication error, or reset them.
D0E3
H
Own station No. out of range
Add station information of the Ethernet adapter module to Network
Configuration Setting of the master station.
Содержание NZ2GF-ETB
Страница 1: ...CC Link IE Field Network Ethernet Adapter Module User s Manual NZ2GF ETB ...
Страница 2: ......
Страница 49: ...47 CHAPTER 4 PROCEDURE BEFORE THE OPERATION 4 4 1 Start Up Procedure Memo ...
Страница 82: ...80 10 The following dialog box is displayed 11 Set the switch on the Ethernet adapter module to RUN Click ...
Страница 198: ...196 a Detail Setting ...
Страница 246: ...244 Memo ...
Страница 253: ......