CHAPTER 7 COMMUNICATION OF THE ETHERNET ADAPTER MODULE
7
7.
2
Com
m
unicat
ion Us
in
g t
he O
n-dem
and
F
unc
tion
(5) Setting data
(a) Connection No.
Set the connection No. where on-demand data is sent from the Ethernet adapter module.
If any number other than those described above is set, a connection No. error (error code: 420
H
) occurs. (
*1
This corresponds to the connection No. in the connection setting in the configuration tool. (
(b) Frame setting format
Specify whether a serial No. is added to on-demand data.
If any number other than those described above is set, a frame setting format error (error code: 421
H
) occurs.
(
(c) Serial No.
Set the serial No. added to the subheader of on-demand data.
The serial No. is effective only when the frame setting format is set to the serial No. added (1
H
).
When the communication data code set in the connection setting is an ASCII code, the setting value is
converted from the binary data to the ASCII code and sent.
(d) Communication data code specification (when using the auto-open UDP port)
Set the communication data code required when using the auto-open UDP port.
(When using TCP, follow the connection setting in the configuration tool.)
If any number other than those described above is set, a communication data code specification error (error
code: 422
H
) occurs. (
Connection
Setting value
Connection for users
1 to 32
Auto-open UDP port
0
Frame setting format
Setting value
No serial No. added
0
H
Serial No. added
1
H
ASCII conversion specification
Setting value
Binary code communication
0
H
ASCII code communication
1
H
Содержание NZ2GF-ETB
Страница 1: ...CC Link IE Field Network Ethernet Adapter Module User s Manual NZ2GF ETB ...
Страница 2: ......
Страница 49: ...47 CHAPTER 4 PROCEDURE BEFORE THE OPERATION 4 4 1 Start Up Procedure Memo ...
Страница 82: ...80 10 The following dialog box is displayed 11 Set the switch on the Ethernet adapter module to RUN Click ...
Страница 198: ...196 a Detail Setting ...
Страница 246: ...244 Memo ...
Страница 253: ......