220
SW0064
Connection status (own
station)
The connection status of the own station is stored.
00
H
: Normal
01
H
: Normal (communicating on PORT1, cable disconnected on PORT2)
04
H
: Normal (loopback communicating on PORT1, cable disconnected on PORT2)
10
H
: Normal (cable disconnected on PORT1, communicating on PORT2)
11
H
: Disconnected (cables disconnected on PORT1 and PORT2)
12
H
: Disconnected (cable disconnected on PORT1, PORT2 line being established)
21
H
: Disconnected (PORT1 line being established, cable disconnected on PORT2)
22
H
: Disconnected (PORT1 and PORT2 lines being established)
40
H
: Normal (cable disconnected on PORT1, loopback communicating on PORT2)
Number
Name
Description