172
D200
H
Double transient data received
• From the master station, check the network condition by CC-Link IE Field
Network diagnostics of GX Works2, and take action.
• Check if the cables and the switching hub are connected properly.
• If the request source resides in another network, check if the routing
parameters are correctly set, and take corrective action.
D201
H
Header information error in transient
data
Correct the header information at the transient request source, and retry the
operation.
D202
H
Send buffer full
• Reduce the frequency of transient transmission and then retry the
operation.
• When the mode of the master station is "Online (High Speed Mode)",
change it to "Online (Normal Mode)" and retry the operation.
• Check if the cables and switching hub are connected properly.
D203
H
Read/write address error in transient
data
Correct the read or write address at the transient request source, and retry
the operation.
D204
H
Network No. error in transient data
• Check and correct the network number at the transient request source,
and retry the operation.
• If the request source resides in another network, check if the routing
parameters are correctly set, and take corrective action.
D205
H
Target station No. error in transient
data
Correct the target station number at the transient request source, and retry
the operation.
D206
H
Network No. error in transient data
• Check and correct the network number at the transient request source,
and retry the operation.
• If the request source resides in another network, check if the routing
parameters are correctly set, and take corrective action.
D207
H
Incorrect number of relays specified in
transient data
• Correct the system configuration to reduce the number of relay stations to
seven or less.
• Check if the routing parameters are correctly set, and take corrective
action.
D208
H
Network No. error in transient data
• Check and correct the network number at the transient request source,
and retry the operation.
• If the request source resides in another network, check if the routing
parameters are correctly set, and take corrective action.
D209
H
to D20A
H
Target station No. error in transient
data
Check and correct the target station number at the transient request source,
and retry the operation.
D20B
H
Specified master station No. error in
transient data
D20C
H
Current master station No. error in
transient data
D20D
H
Transient data transmission
completion wait timeout
• From the master station, check the network condition by CC-Link IE Field
Network diagnostics of GX Works2, and take action.
• If the originating or target station has detected an error, identify the cause
of the error and take action.
• Reduce the frequency of transient transmission and then retry the
operation.
• When the mode of the master station is "Online (High Speed Mode)",
change it to "Online (Normal Mode)" and retry the operation.
• Check if the cable of the request source and the switching hub are
connected properly.
D20E
H
Header information error in transient
data
Correct the header information at the transient request source, and retry the
operation.
D20F
H
Target station No. error in transient
data
Check the command at the transient request source to see if it is available
for all stations or a group, and retry the operation.
D210
H
Target station No. error in transient
data
Correct the header information at the transient request source, and retry the
operation.
Error code
Error
Action
Содержание NZ2GF-ETB
Страница 1: ...CC Link IE Field Network Ethernet Adapter Module User s Manual NZ2GF ETB ...
Страница 2: ......
Страница 49: ...47 CHAPTER 4 PROCEDURE BEFORE THE OPERATION 4 4 1 Start Up Procedure Memo ...
Страница 82: ...80 10 The following dialog box is displayed 11 Set the switch on the Ethernet adapter module to RUN Click ...
Страница 198: ...196 a Detail Setting ...
Страница 246: ...244 Memo ...
Страница 253: ......