174
D282
H
Receive queue full
• From the master station, check the network condition by CC-Link IE Field
Network diagnostics of GX Works2, and take action.
• When the receiving station encountered overloading of transient data,
send the data from the source after a given time has elapsed.
D283
H
Transient transmission failed
• From the master station, check the network condition by CC-Link IE Field
Network diagnostics of GX Works2, and take action.
• Exchange the cables between PORT1 and PORT2 at the request source
and retry the operation.
• Reduce the frequency of transient transmission and then retry the
operation.
D2A0
H
Receive buffer full
• From the master station, check the network condition by CC-Link IE Field
Network diagnostics of GX Works2, and take action.
• When the receiving station encountered overloading of transient data,
send the data from the source after a given time has elapsed.
D2A1
H
Send buffer full
• Reduce the frequency of transient transmission and then retry the
operation.
• Check if the cable of the request source and the switching hub are
connected properly.
D2A2
H
Transmission completion wait timer
timeout
• Reduce the frequency of transient transmission and then retry the
operation.
• Check if the cable of the request source and the switching hub are
connected properly.
D2A3
H
Data length error in transient data
Correct the data size (frame length) at the transient request source, and retry
the operation.
D2A4
H
Header information error in transient
data
Correct the header information at the transient request source, and retry the
operation.
D2A5
H
Target station No. error in transient
data
Correct the target station number at the transient request source, and retry
the operation.
D2A6
H
Transient data request source No.
error
Correct the request source number at the transient request source, and retry
the operation.
D2A7
H
to D2A8
H
Header information error in transient
data
Correct the header information at the transient request source, and retry the
operation.
D2A9
H
Target network No. error in transient
data
Correct the target network number at the transient request source, and retry
the operation.
D2AA
H
Target station No. error in transient
data
Correct the target station number at the transient request source, and retry
the operation.
D2AB
H
Network No. error in transient data
Correct the request source network number at the transient request station,
and retry the operation.
D2AC
H
Transient data request source No.
error
Correct the request source station number at the transient request station,
and retry the operation.
D2AD
H
Data length error in transient data
Correct the data size (frame length) at the transient request station, and retry
the operation.
D2AE
H
Target station No. error in transient
data
• The Ethernet adapter module received transient data addressed to a
different network. Check the network and target station numbers, and retry
the operation.
• Check if the routing parameters are correctly set.
D2AF
H
Target station No. error in transient
data
• Transient data addressed to the own station were sent. Check the network
and target station numbers, and retry the operation.
• Check if the routing parameters are correctly set.
Error code
Error
Action
Содержание NZ2GF-ETB
Страница 1: ...CC Link IE Field Network Ethernet Adapter Module User s Manual NZ2GF ETB ...
Страница 2: ......
Страница 49: ...47 CHAPTER 4 PROCEDURE BEFORE THE OPERATION 4 4 1 Start Up Procedure Memo ...
Страница 82: ...80 10 The following dialog box is displayed 11 Set the switch on the Ethernet adapter module to RUN Click ...
Страница 198: ...196 a Detail Setting ...
Страница 246: ...244 Memo ...
Страница 253: ......