168
0991
H
[ADAPTER UNIT DOWN]
• The buffer memory size of the Ethernet part is abnormal.
• No response is returned from the Ethernet part.
■
Supplementary information
• Common information: -
• Individual information: -
■
Diagnostic timing
• When powered on or reset
The hardware of the Ethernet adapter module may be faulty.
Please consult your local Mitsubishi representative.
RUN: Flashing
ERR.: On
0993
H
[ADAPTER UNIT DOWN]
• No response is returned from the Ethernet part.
• Failure of the Ethernet part was detected.
■
Supplementary information
• Common information: -
• Individual information: -
■
Diagnostic timing
• Any time
09F4
H
[DC DOWN]
• Momentary supply power failure occurred.
• The supply power turned off.
■
Supplementary information
• Common information: -
• Individual information: -
■
Diagnostic timing
• Any time
Check the supply power.
RUN: On
ERR.: Off
0A62
H
[FLASH ROM ERROR]
The number of writes to the parameter memory exceeded
100,000 times. (Number of writes > 100,000)
■
Supplementary information
• Common information: -
• Individual information: -
■
Diagnostic timing
• When writing data to ROM
Replace the Ethernet adapter module.
RUN: On
ERR.: On
0ABC
H
[BUS TIMEOUT ERR.]
Failure of the system bus was detected.
• Self-diagnostic error of the system bus
• Self-diagnostic error of the Ethernet adapter module
■
Supplementary information
• Common information: -
• Individual information: -
■
Diagnostic timing
• Any time
Reset the Ethernet adapter module.
If this error occurs again, the hardware of the Ethernet
adapter module may be faulty. Please consult your local
Mitsubishi representative.
RUN: Flashing
ERR.: On
0AC6
H
[UNIT BUS ERROR]
Failure of the system bus was detected.
■
Supplementary information
• Common information: -
• Individual information: -
■
Diagnostic timing
• Any time
0ADA
H
[SYSTEM RST ERR.]
Failure of the system bus was detected.
■
Supplementary information
• Common information: -
• Individual information: -
■
Diagnostic timing
• When powered on or reset
Reset the Ethernet adapter module.
If this error occurs again, the hardware of the Ethernet
adapter module may be faulty. Please consult your local
Mitsubishi representative.
RUN: Flashing
ERR.: On
0C10
H
[UNIT HW ERROR]
Hardware failure was detected.
■
Supplementary information
• Common information: -
• Individual information: -
■
Diagnostic timing
• Any time
Reset the Ethernet adapter module.
If this error occurs again, the hardware of the Ethernet
adapter module may be faulty. Please consult your local
Mitsubishi representative.
RUN: Flashing
ERR.: On
Error
code
Error and cause
Action
LED status
Содержание NZ2GF-ETB
Страница 1: ...CC Link IE Field Network Ethernet Adapter Module User s Manual NZ2GF ETB ...
Страница 2: ......
Страница 49: ...47 CHAPTER 4 PROCEDURE BEFORE THE OPERATION 4 4 1 Start Up Procedure Memo ...
Страница 82: ...80 10 The following dialog box is displayed 11 Set the switch on the Ethernet adapter module to RUN Click ...
Страница 198: ...196 a Detail Setting ...
Страница 246: ...244 Memo ...
Страница 253: ......