6 OPTIONS AND PERIPHERAL EQUIPMENT
6.13 Noise reduction techniques
■
Cable clamp fitting AERSBAN-_SET
Generally, connecting the grounding wire of the shielded wire to the SD terminal of the connector provides a sufficient effect.
However, the effect can be increased when the shielded wire is connected directly to the ground plate as shown below.
Install the ground plate near the servo amplifier for the encoder cable. Peel part of the cable insulator to expose the external
conductor, and press that part against the ground plate with the cable clamp. If the cable is thin, clamp several cables in a
bunch.
The cable clamp comes as a set with the grounding plate.
[Unit: mm]
• Dimensions
[Unit: mm]
*1 Screw hole for grounding. Connect it to the ground plate of the cabinet.
Precautions
• The motor cable (single cable type) has no shield on the outermost circumference. Therefore, to ground the motor cable
with a cable clamp, use a motor cable (dual cable type).
Model
A
B
C
Accessory fittings
AERSBAN-DSET
100
86
30
Clamp A: 2pcs.
AERSBAN-ESET
70
56
Clamp B: 1pc.
Clamp fitting
L
A
70
B
45
40
Strip the cable insulator
of the clamped area.
Cutter
Cable
Clamp fittings
(A, B)
Grounding plate
Cable
External conductor
Clamp section diagram
11
24
0
3
7
35
C A
17.5
6
35
22
6
B ± 0.3
30
10
24
+0.3
0
-0.2
Grounding plate
Clamp fitting
2-φ5 hole
Mounting hole
L or less
M4 screw
*1