5 - 3
5. PARAMETERS
5.1.3 Selection of regenerative brake option
Parameter
No.
Symbol
Name
Initial Value
Unit
Setting Range
PA02
**REG Regenerative brake option
0000h
Refer to the text.
POINT
This parameter value and switch power off once, then switch it on again to
make that parameter setting valid.
Wrong setting may cause the regenerative brake option to burn.
If the regenerative brake option selected is not for use with the servo
amplifier, parameter error (37) occurs.
Set this parameter when using the regenerative brake option.
Selection of regenerative brake option
00: Regenerative brake option is not used
For MR-J3-10B, regenerative brake resistor is not used.
For MR-J3-20B or more, built-in regenerative brake resistor is used.
01: FR-BU FR-RC
02: MR-RB032
03: MR-RB12
04: MR-RB32
05: MR-RB30
06: MR-RB50
08: MR-RB31
09: MR-RB51
0 0
Parameter No. PA02
5.1.4 Using absolute position detection system
Parameter
No.
Symbol
Name
Initial Value
Unit
Setting Range
PA03
*ABS
Absolute position detection system
0000h
Refer to the text.
POINT
This parameter is made valid when power is switched off, then on after
setting, or when the controller reset has been performed.
This parameter cannot be used in the speed control mode.
Set this parameter when using the absolute position detection system in the position control mode.
Selection of absolute position detection system (refer to Chapter 12)
0: Used in incremental system
1: Used in absolute position detection system
Parameter No. PA03