11. OPTIONS AND AUXILIARY EQUIPMENT
11.9 No-fuse breakers, fuses, magnetic contactors
Always use one no-fuse breaker and one magnetic contactor with one servo amplifier. When using a fuse
instead of the no-fuse breaker, use the one having the specifications given in this section.
Fuse
Servo amplifier
No-fuse breaker
(Note) Class
Current [A]
Voltage [V]
Magnetic contactor
MR-J3-10B (1)
30A frame 5A
K5
10
MR-J3-20B
30A frame 5A
K5
10
MR-J3-40B
20B1
30A frame 10A
K5
15
MR-J3-60B
70B
100B
40B1
30A frame 15A
K5
20
S-N10
MR-J3-200B
30A frame 20A
K5
40
S-N18
MR-J3-350B
30A frame 30A
K5
70
S-N20
MR-J3-500B
50A frame 50A
K5
125
S-N35
MR-J3-700B
100A frame 75A
K5
150
AC250
S-N50
Note. This servo amplifier is UL/C-UL-listed when using a Class T fuse. Therefore, when using the servo amplifier as a UL/C-UL
Standard compliant product, be sure to use the Class T fuse.