242
6 OPTIONS AND PERIPHERAL EQUIPMENT
6.14 Noise reduction techniques
■
Noise reduction techniques for the network cable
Take measures against noise for both ends of the network cable.
If using the network cable in an environment with excessive noise, directly connect the shield of the cable to the ground plate
with cable clamp fittings at a place 200 mm to 300 mm or less from the servo amplifier.
When connecting the network cable from outside the cabinet, connect it to the ground plate at a place 5 mm to 10 mm away
from the cabinet entrance.
To reinforce noise reduction techniques, installing a data line filter (TDK ZCAT1730-0730) to the network cable is
recommended. Install the data line filter to a place 80 mm or less from the servo amplifier.
• Inside the cabinet
When using cable clamp fittings
When using a data line filter
Servo amplifier
Cable clamp fitting
200 mm to 300 mm
Servo amplifier
Data line filter
80 mm or less
Содержание MELSERVO-J5 MR-J5-G Series
Страница 1: ...MR J5 User s Manual Hardware MR J5 _G_ MR J5W_ _G_ MR J5 _A_ Mitsubishi Electric AC Servo System ...
Страница 2: ......
Страница 473: ...12 USING A FULLY CLOSED LOOP SYSTEM 12 7 Absolute position detection system 471 12 MEMO ...
Страница 477: ......