5 MODULE DEDICATED INSTRUCTION
5.4 Network Dedicated Instruction
185
5
Writing to buffer memory of intelligent function module on
remote I/O station
Z(P)_REMTO
The following instruction can go in the dotted squares.
Z_REMTO, ZP_REMTO
■
Executing condition
■
Argument
Instruction
Executing condition
Z_REMTO
ZP_REMTO
Input/output
argument
Name
Description
Data type
Input argument
EN
Executing condition
Bit
Jn*
Network number of the host station (1 to 239)
String
n1
Channel number
CC-Link IE Field Network: 1 to 32
MELSECNET/H: 1 to 8
ANY16
n2
Target station number
CC-Link IE Field Network: 1 to 120
MELSECNET/H: 1 to 64
ANY16
n3
Start I/O number of the target intelligent function
module
For the CC-Link IE Field Network,
the higher two digits when expressing the I/O
number in three digits.
For the MELSECNET/H,
the higher three digits when expressing the I/O
number in four digits.
ANY16
n4
Write buffer memory start address
Specifies the start address of the buffer memory for
the write destination intelligent function module.
ANY16
n5
Number of write points
CC-Link IE Field Network: 1 to 240
MELSECNET/H: 1 to 960
ANY16
CC IE F NET/H
Structured ladder/FBD
EN
ENO
Jn*
d1
d2
n1
n2
n3
n4
n5
Z_REMTO
ST
Z_REMTO
(EN, Jn*, n1, n2, n3, n4, n5, d1, d2);
ENO:=
Содержание MELSEC System Q
Страница 1: ...MELSEC Q L Structured Programming Manual Special Instructions ...
Страница 2: ......
Страница 307: ...10 SFC CONTROL INSTRUCTION 10 2 SFC Transition Condition Comment Read 305 10 MEMO ...
Страница 309: ...I 307 MEMO ...
Страница 315: ......