238
6 PID CONTROL INSTRUCTION
6.1 PID Control Instruction (Inexact Differential)
Setting data
Device
Data item
Description
Setting range
Setting
side
Processing when the
setting data are outside
the setting range
With PID limits
Without PID
limits
(s)+0
Operational
expression
selection
Select the PID operational
expression.
0: Forward
operation
1: Reverse
operation
0: Forward
operation
1: Reverse
operation
User
An error occurs and the PID
operation for the
corresponding loop is not
performed.
(s)+1
Sampling cycle
(T
S
)
Set the PID operation cycle.
1 to 6000
(unit: 10ms)
1 to 6000
(unit: 10ms)
User
(s)+2
Proportional
constant (K
P
)
Proportional gain of PID
operation
1 to 10000
(unit: 0.01)
1 to 10000
(unit: 0.01)
User
An error occurs and the PID
operation for the
corresponding loop is not
performed.
(s)+3
Integral constant
(T
I
)
Constant that expresses the
magnitude of the integral
action (I action) effect.
Increasing the integral
constant slows down the
manipulated value change.
1 to 32767
(unit: 100ms)
If setting value
> 30000
T
I
= Infinite (
)
1 to 32767
(unit: 100ms)
If setting value
> 30000
T
I
= Infinite (
)
User
(s)+4
Derivative constant
(T
D
)
Constant that expresses the
magnitude of the derivative
action (D action) effect.
Increasing the derivative
constant causes significant
changes in the manipulated
value even with a slight
change of the control target.
0 to 30000
(unit: 10ms)
0 to 30000
(unit: 10ms)
User
(s)+5
Filter coefficient (
)
Set the degree of filtering to
be applied to the process
value.
The filtering effect decreases
as the value gets closer to 0.
0 to 100
0 to 100
User
(s)+6
MV lower limit
(MVLL)
Set the lower limit for the
manipulated value (MV)
calculated in PID operation in
automatic mode.
If the MV is less than the set
lower limit value (MVLL), the
value is clipped to the MVLL.
-50 to 2050
-32768 to 32767
User
In the case of "With PID
limits", the PID operation is
performed after values are
replaced as follows:
• If MVLL or MVHL value is
less than -50, the value is
clipped to -50.
• If MVLL or MVHL value is
greater than 2050, the
value is clipped to 2050.
(s)+7
MV upper limit
(MVHL)
Set the upper limit for the
manipulated value calculated
in PID operation in automatic
mode.
If the MV is greater than the
set upper limit value (MVHL),
the value is clipped to the
MVHL.
-50 to 2050
-32768 to 32767
User
(s)+8
MV change rate
limit (
MVL)
Set the variation limit
between the previous MV
and the present MV.
When the MV variation is
greater than the limit value,
bit 1 (b1) of the alarm device
is set to '1'.
MV variation is not limited.
(Even if the MV variation
exceeds the limit value, the
actual MV variation is used
as it is for calculating the
MV.)
0 to 2000
-32768 to 32767
User
In the case of "With PID
limits", the PID operation is
performed after values are
replaced as follows:
• If the
MVL value is less
than 0, the value is clipped
to 0.
• If the
MVL value is
greater than 2000, the
value is clipped to 2000.
Содержание MELSEC System Q
Страница 1: ...MELSEC Q L Structured Programming Manual Special Instructions ...
Страница 2: ......
Страница 307: ...10 SFC CONTROL INSTRUCTION 10 2 SFC Transition Condition Comment Read 305 10 MEMO ...
Страница 309: ...I 307 MEMO ...
Страница 315: ......